background image

Safety 

Precautions

 Page 10

 

 

 

 

 

    cylinders. (No more than 80 % volume liquid charge).     i)  Do not exceed the maximum working 

    pressure of thecylinder, even temporarily.     j)  When the cylinders have been filled correctly and the 

    process completed, make sure that the cylinders and the equipment are removed from site promptly 

    and all isolation valves on the equipment are closed off.     k) Recovered refrigerant shall not be charged 

    into another refrigeration  system unless it has been cleaned and checked.

15.Labelling

    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The 

    label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment 

    contains flammable refrigerant.

16.Recovery

    When removing refrigerant from a system, either for servicing or decommissioning, it is recommended 

    good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, 

    ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct 

    number of cylinders for holding the total system charge is available. All cylinders to be used are 

    designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the 

    recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off 

    valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before 

    recovery occurs. The recovery equipment shall be in good working order with a set of instructions 

    concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. 

    In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall 

    be complete with leak-free disconnect couplings and in good condition. Before using the recovery 

    machine, check that it is in satisfactory working order, has been properly maintained and that any 

    associated electrical components are sealed to prevent ignition in the event of a refrigerant release. 

    Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier 

    in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants 

    in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, 

    ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant 

    does not remain within the lubricant. The evacuation process shall be carried out prior to returning the 

    compressor to the suppliers. Only electric heating to the compressor body shall be employed to 

    accelerate this process. When oil is drained from a system, it shall be carried out safely. 

Before carrying out this procedure, it is essential that the technician is completely familiar with the 

equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 

Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is 

required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before 

the task is commenced. 

14.Decommissioning

a) Become familiar with the equipment and its operation.    b) Isolate system electrically.    c) Before 

attempting the procedure ensure that: Mechanical handling equipment is available, if required, for 

handling refrigerant cylinders;All personal protective equipment is available and being used correctly; 

The recovery process is supervised at all times by a competent person; Recovery equipment and 

cylinders conform to the appropriate standards.    d) Pump down refrigerant system, if possible.    e) If a 

vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of  the

system.     f) Make sure that cylinder is situated on the scales before recovery takes place.    g) Start the 

recovery machine and operate in accordance with manufacturer's instructions.    h) Do not overfill 

Summary of Contents for MDDF-16

Page 1: ...DEHUMIDIFIER Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new machine Make sure to save this manual for future reference...

Page 2: ...ance Table of Contents Control Panel Features 12 Other features 15 Clean the grille and case 18 Clean the bucket 18 Troubleshooting Tips 19 Clean the air filter 18 When not using the unit for long tim...

Page 3: ...the unit Do not use the machine near flammable gas or combustibles such as gasoline benzene thinner etc Do not drink or use the water drained from the unit Do not take the water bucket out during oper...

Page 4: ...been damaged contact a technician or customer service for assistance In a thunderstorm the power must be cut o to avoid damage to the machine due to lightning Do not run cord under carpeting Do not c...

Page 5: ...of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in domestic household waste For disposal there are several possibilities When using this dehu...

Page 6: ...manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants The appl...

Page 7: ...able material 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flamma...

Page 8: ...supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing t...

Page 9: ...ions on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 10 Detection of flammable refrigerants The fo...

Page 10: ...g order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered r...

Page 11: ...prior notice Preparation rear front rear front rear front control panel control panel shoes dryer cover shoes dryer pipe drain hose outlet drain hose outlet drain hose outlet power cord buckle power c...

Page 12: ...to help prevent moisture damage The dehumidifier must be operated in an enclosed area to be most effective Close all doors windows and other outside openings to the room A dehumidifier operating in a...

Page 13: ...s Then press pad to operate the desired settings For panel H Indicator Function Indicator Function Timer ON light Timer OFF light Bucket full light Air purifier light Low fan speed light Med fan speed...

Page 14: ...fan control to Normal Note The turbo button is disabled in Dryer mode the Self clean Air purifier or Anti mould functions Pressing the turbo button for more than 3 seconds enables the Self clean funct...

Page 15: ...midity sensor error Unplug the unit and plug it back in If error repeats call for service ES Temperature sensor error Unplug the unit and plug it back in If error repeats call for service P2 Bucket is...

Page 16: ...on will also be cancelled There are two ways to remove collected water 1 Use the bucket When the unit is off if the bucket is full the unit will beep 8 times on some models and the Full Water indicato...

Page 17: ...the drain hose Select the desired humidity setting and fan speed on the unit for continuous draining to start 2 Continuous draining Note When the continuous drain feature is not being used remove the...

Page 18: ...urely seated for the dehumidifier to operate The air filter behind the front grille should be checked and cleaned at least every two weeks or more often if necessary NOTE DO NOT RINSE OR PUT THE FILTE...

Page 19: ...upright as it should be The floor surface is not level Hose to connector or hose connection may be loose Intend to use the bucket to collect water but the back drain plug is removed This is normal The...

Page 20: ...s are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please...

Reviews: