background image

Safety 

Precautions

 Page 9

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will 

not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe 

components are the only types that can be worked on while live in the presence of a flammable 

atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts 

specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere 

from a leak.

8.Repair to intrinsically safe components 

 

and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 

maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and 

corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 

the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 

Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 

brazing process.  

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 

procedures shall be used. However, it is important that best practice is followed since flammability is a 

consideration. The following procedure shall be adhered to:

Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the 

circuit by cutting or brazing.   

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed 

with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or 

10.Detection of flammable refrigerants

The following leak detection methods are deemed acceptable for systems containing flammable 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a 

refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for 

the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

11.Leak detection methods

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or 

any other adverse environmental effects. The check shall also take into account the effects of aging or 

continual vibration from sources such as compressors or fans.

9.Cabling

12.Removal and evacuation

Under no circumstances shall potential sources of ignition be used in the searching for or detection 

of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

 

being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an 

electrical supply to equipment during servicing, then a permanently operating form of leak detection 

shall be located at the most critical point to warn of a potentially hazardous situation. 

2)Particular attention shall be paid to the following to ensure that by working on electrical components, 

the casing is not altered in such a way that the level of protection is affected. This shall include damage 

to cables, excessive number of connections, terminals not made to original specification, damage to 

seals, incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure that seals or 

sealing materials have not degraded such that they no longer serve the purpose of preventing the 

ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's 

specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection 

equipment. Intrinsically safe components do not have to be isolated prior to working on them.

Summary of Contents for 373127

Page 1: ...TIONER Local Air Conditioner Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual fo...

Page 2: ...ecautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust...

Page 3: ...grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your unit...

Page 4: ...ould be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the su...

Page 5: ...Wild disposal of waste in forests and landscapes endangers your health when hazar do us substances leak into the ground water and find their way into the food chain Do not use hazardous chemicals to c...

Page 6: ...e use of flammable refrigerants AVERTISSEMENT Ne pas utiliser de produits permettant d acc l rer le d gel ou de produits de nettoyage autres que ceux recommand s par le fabricant L appareil doit tre e...

Page 7: ...side the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 3 General work area A...

Page 8: ...uit is being used the secondary circuit shall be checked for the presence of refrigerant Marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be cor...

Page 9: ...e following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may...

Page 10: ...Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment i...

Page 11: ...y Installation Instructions Preparation NOTE All the illustrations in the manual are for explanation purpose only Your machine may be slightly different The actual shape shall prevail The unit can be...

Page 12: ...this could cause damage to the unit 50cm 19 7 inch 30cm 30cm 12inch 12inch 50cm 19 7inch Energy Rating Information The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts Diam...

Page 13: ...ving the air feeling damp To find the proper air conditioner determine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditi...

Page 14: ...der A Bolt 1 pc 1 set Unit Adaptor Security Bracket and 2 Screws 1 pc 1 pc Exhaust Hose Drain Hose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T IM...

Page 15: ...he Adjustable Window Slider or or Window slider A MODEL A MODEL B Window slider B Bolt Window slider A Window slider B Bolt MODEL A MODEL B MODEL C MODEL D 1 2 Window slider A Window slider B Window s...

Page 16: ...m to the window sash and frame as shown 2 Insert the window slider assembly into the window opening Or Foam seal B Adhesive type shorter Foam seal A Adhesive type Foam seal B Adhesive type shorter Foa...

Page 17: ...he wall for the Wall Exhaust Adaptor B 2 Secure the Wall Exhaust Adaptor B to the wall using the four Anchors and Screws provided in the kit 3 Connect the Exhaust Hose Assembly with Wall Exhaust Adapt...

Page 18: ...8 minutes the unit exits Wireless connection mode automatically After Wireless connection is successful you can press and hold SWING and DOWN buttons at the same time for 3 seconds to turn off Wirele...

Page 19: ...the set temperature in C or F F no display for some models and the Auto timer settings While on DRY and FAN modes it shows the room temperature Shows Error codes and protection code E1 Room temperatu...

Page 20: ...Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time re...

Page 21: ...ut drain connector just attach the drain hose to the hole Place the open end of the Hose adaptor directly over the drain area in your basement floor that there are no kinks that will stop the warter f...

Page 22: ...nit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the appliance on FAN mode for 12 hours in a warm room to dry it and pre...

Page 23: ...if possible The unit is noisy and vibrates too much The unit makes a gurgling sound The ground is not level Place the unit on a flat level surface The air filter is blocked with dust or animal hair Tu...

Page 24: ...and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the servi...

Reviews: