background image

 Page 12 

 Installation

Instructions

MODE

Temperature Range

MODE

Temperature Range

Ambient Temperature Range For Unit Operating

Cool 

    17-35°C (62-95°F)

Dry 

Heat(pump heat mode) 
Heat(electrical heat mode) 

    13-35°C (55-95°F)

    5-30°C (41-86°F)

Exhaust Hose Installation

The exhaust hose and adaptor must be installed or removed in accordance with the usage mode. For 

COOL,HEAT(heat pump type) or AUTO mode must be installed exhaust hose. For FAN, DRY or HEAT

(electrical heat type) mode must be removed exhaust hose.

30°C (86°F)

Choosing The Right Location

Recommend Installation

Your installation location should meet the following requirements:

-Make sure that you install your unit on an even surface to minimize noise and 

 vibration. 

-The unit must be installed near a grounded plug, and the Collection Tray Drain 

 (found on the back of the unit) must be accessible. 

-The unit should be located at least 30cm (12”) from the nearest wall to ensure 

 proper air conditioning. The horizontal louver blade should be at least 50cm

 (19.7”) away from obstacles.

-DO NOT cover the Intakes, Outlets or Remote Signal Receptor of the unit, as this 

 could cause damage to the unit. 

50cm

19.7 inch

30cm

30cm

12inch

12inch

50cm

19.7inch

Energy Rating Information

 

The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts(Diameter:150mm, Length:1.5m 

+ Diameter: 130mm, Length: 1.5m) 

.

The Energy rating and noise information for unit with 3 meters extended 

exhaust duct is not assessed.(For some models)

NOTE

 

We recommend that operating the unit at room temperature below 35

°C

 . Since there is a risk that the unit with 3 

meters extended exhaust duct would not work at room temperature above 35

°C 

under some extreme conditions, 

such as the lower air intake be blocked for 50%.      

The energy rating and noise information for this unit is based on the standard installation using an un-extended 

exhaust duct (Diameter:150mm, Length:1.5m) without window slider adaptor or wall exhaust adaptor A. 

How to Stay Cool with a New Portable Air Conditioner(For the models comply with the 

requirements of Department Of Energy in US)

Because of a new federal test procedure for Portable Air Conditioners, you may notice that the 

cooling capacity claims on portable air conditioner packaging are significantly lower than that of

models produced prior to 2017. This is due to changes in the test procedure, not to the portable 

air conditioners themselves.

Summary of Contents for 373127

Page 1: ...TIONER Local Air Conditioner Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual fo...

Page 2: ...ecautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust...

Page 3: ...grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your unit...

Page 4: ...ould be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the su...

Page 5: ...Wild disposal of waste in forests and landscapes endangers your health when hazar do us substances leak into the ground water and find their way into the food chain Do not use hazardous chemicals to c...

Page 6: ...e use of flammable refrigerants AVERTISSEMENT Ne pas utiliser de produits permettant d acc l rer le d gel ou de produits de nettoyage autres que ceux recommand s par le fabricant L appareil doit tre e...

Page 7: ...side the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 3 General work area A...

Page 8: ...uit is being used the secondary circuit shall be checked for the presence of refrigerant Marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be cor...

Page 9: ...e following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may...

Page 10: ...Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment i...

Page 11: ...y Installation Instructions Preparation NOTE All the illustrations in the manual are for explanation purpose only Your machine may be slightly different The actual shape shall prevail The unit can be...

Page 12: ...this could cause damage to the unit 50cm 19 7 inch 30cm 30cm 12inch 12inch 50cm 19 7inch Energy Rating Information The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts Diam...

Page 13: ...ving the air feeling damp To find the proper air conditioner determine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditi...

Page 14: ...der A Bolt 1 pc 1 set Unit Adaptor Security Bracket and 2 Screws 1 pc 1 pc Exhaust Hose Drain Hose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T IM...

Page 15: ...he Adjustable Window Slider or or Window slider A MODEL A MODEL B Window slider B Bolt Window slider A Window slider B Bolt MODEL A MODEL B MODEL C MODEL D 1 2 Window slider A Window slider B Window s...

Page 16: ...m to the window sash and frame as shown 2 Insert the window slider assembly into the window opening Or Foam seal B Adhesive type shorter Foam seal A Adhesive type Foam seal B Adhesive type shorter Foa...

Page 17: ...he wall for the Wall Exhaust Adaptor B 2 Secure the Wall Exhaust Adaptor B to the wall using the four Anchors and Screws provided in the kit 3 Connect the Exhaust Hose Assembly with Wall Exhaust Adapt...

Page 18: ...8 minutes the unit exits Wireless connection mode automatically After Wireless connection is successful you can press and hold SWING and DOWN buttons at the same time for 3 seconds to turn off Wirele...

Page 19: ...the set temperature in C or F F no display for some models and the Auto timer settings While on DRY and FAN modes it shows the room temperature Shows Error codes and protection code E1 Room temperatu...

Page 20: ...Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time re...

Page 21: ...ut drain connector just attach the drain hose to the hole Place the open end of the Hose adaptor directly over the drain area in your basement floor that there are no kinks that will stop the warter f...

Page 22: ...nit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the appliance on FAN mode for 12 hours in a warm room to dry it and pre...

Page 23: ...if possible The unit is noisy and vibrates too much The unit makes a gurgling sound The ground is not level Place the unit on a flat level surface The air filter is blocked with dust or animal hair Tu...

Page 24: ...and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the servi...

Reviews: