If, on a call for heat, flame ignition does not occur, refer to the 

trouble chart

for further

information.

If leakage through the valve occurs, as evidenced by the presence of flame on standby,

the entire valve must be replaced.

If the combination valve has been moved or replaced, soap bubble test for leaks with the

burner running.

______________________________________________________

The Electronic Control is a 24 volt AC, solid state electronic device that automatically ignites
and monitors the flame. It has an integral high voltage transformer and, upon a call for heat,
applies high voltage to the spark electrode and 24V to the combination valve. When the
flame is proven, the spark is terminated and the burner run continues.

If the flame is not proven within 6 seconds, or if the proof of flame is lost during the

burner run and not re-established within 6 seconds, the Control will shut off the combination
valve and 

lock out

. To 

reset

the Electronic Control for restart, de-energize the Electronic

Control by setting the operating control to 

OFF

or thermostat below room temperature for at

least 30 seconds.

If the Electronic Control is changed, the replacement must be identical as to the make

and model number, or must be an authorized substitute.

WARNING: Explosion hazard.  
Do not use this device if it gets wet. It can malfunction and cause serious 
injury or death. Replace any device that has been wet.

______________________________________________________

Keep the area around the burner clear and free of combustible materials, gasoline or

other flammable liquids or vapors.  Do not obstruct burner air openings or ventilation grills
for combustion air.

The motor features permanently lubricated ball bearings and requires no routine oiling

maintenance.

IMPORTANT: Check the burner flame periodically. A proper NATURAL gas flame will appear
blue at the burner face with orange and yellow tips. A proper PROPANE gas flame will
appear blue at the burner face with yellow tips. If the flame is too rich, it will appear billowy
and yellow with hazy tips. If too lean, it will appear short and all blue. If the flame does not
appear proper, CONTACT A QUALIFIED SERVICE TECHNICIAN FOR CLEANING
AND/OR READJUSTMENT.

WARNING: If any flame is observed when the burner is on standby, or if the

ignition spark or valve operator is heard to come on before the motor reaches
operating speed, immediately turn off the manual gas control and burner power. A
dangerous  condition has developed and must be corrected. CONTACT A QUALIFIED
SERVICE TECHNICIAN FOR CLEANING, READJUSTMENT OR REPAIR.

Part 2 Service

Part 2

Service 

Continued 

XI Combination Gas Valve

Continued 

Consumer Instruction

Figure 8:

General Assembly

10

Consumer Instruction

Maintenance

XI Electronic 

Control System

Summary of Contents for Economite DS45B

Page 1: ...any other appli ance Installation and service must be per formed by a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call ...

Page 2: ...ular air ducts shall not be less than 3 inches In Canada for detailed ventilation requirements refer to standard CAN 1 B149 1 or 2 and or local codes ______________________________________________________ Clean the gas utilization equipment combustion chamber heat exchanger interior and flue connections Remove all adhering tars scale dirt and soot Inspect for actual leaks and or potential leaks Ce...

Page 3: ... the burner tube is too short to reach the combustion chamber such as old fashioned gravity warm air furnace installations WARNING Burner cabinet must be mounted in orientation shown in Figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangements may be available for some models consult factory for details if requi...

Page 4: ...y In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than the top of the highest flue passage in the equipment Gas utilization equipment requiring controlled draft may be equipped with a listed double acting barometric draft regulator installed and adjusted in accordance with the manufacturer s instructions if approved by local codes A d...

Page 5: ...igure 5 The burner gas supply piping should branch off from the main line as close to the gas meter as possible Do not connect to the bottom of a horizontal section Use new black pipe and malleable fittings free of cutting and threading burrs or defects Provide a sediment trap union and 1 8 pressure tap in piping close to burner as shown in Figure 5 Use pipe joint compound resistant to Liquid Petr...

Page 6: ...apacity spud input The burner is shipped with the primary air controlling shutter set wide open to provide a lean gas air mixture during the initial start up Do not change the combination gas valve pressure regulator setting at this time CAUTION The approximate air and gas settings described above are for initial start up only Final settings must be made in accordance with Section VIII Instruction...

Page 7: ...lization equipment must be off Then Divide by 1 000 for MBH value For PROPANE gas consult your supplier for method of determining firing rate 10 Readjust the primary air shutter to provide a quiet soft blue flame with well defined orange and yellow tips for NATURAL gas or with well defined yellow tips for PROPANE gas 11 Check the operation of the burner start and stop it several times with the the...

Page 8: ...set to its original position following servicing Cleaning of the blower wheel is usually the only service required Need for cleaning is indicated if the air cage assembly shows an accumulation of dust and lint or if the character of the flame indicates a deficiency of air Motor cooling air vents should also be cleaned at this time The blower side plate motor and wheel are removed as an assembly Di...

Page 9: ...ld gas pressure of 3 5 W C for NATURAL If pressure adjustment is required for setting capacity remove regulator cap for access to slotted adjustment screw Turning of adjustment screw counter clockwise reduces pressure clockwise increases pressure Do not adjust past the point where no change in pressure is noted NOTE Pressure setting must be made with burner running and main gas ON CAUTION When adj...

Page 10: ...Do not use this device if it gets wet It can malfunction and cause serious injury or death Replace any device that has been wet ______________________________________________________ Keep the area around the burner clear and free of combustible materials gasoline or other flammable liquids or vapors Do not obstruct burner air openings or ventilation grills for combustion air The motor features per...

Page 11: ...ER LISTED I MOTOR WILL NOT RUN OR MOTOR RUNS IN REPEATED CYCLES A Confirm 120V between strip terminals 1 and 2 and verify the circuit polarity and electrical ground between strip terminal 1 and GND B Check 24V operating control circuit 1 Between left strip terminal T and GND a No voltage transformer defective b Very low voltage circuit overloaded or transformer defective 2 Between right strip term...

Page 12: ...d steady Verify per Section VII that the spud orifice size and manifold pressure are correct b Zero erratic low or high pressure confirm that the inlet pressure to the combination valve is between 5 0 and 14 0 W C for NATURAL 11 0 to 14 0 W C PROPANE during standby and during trial for ignition c If manifold pressure is zero below 1 5 or above 3 5 W C NATURAL 10 0 W C PROPANE or erratic replace co...

Reviews: