3.12.7 Important Notes
The device must be already connected to an active CAN bus at power-on!
Otherwise a CAN error happens at sending the bootup message and it is
not possible to change (immediately) to „OPERATIONAL“!
If it can not be assured that there exists at least one other active CAN bus
member (f.e. the PLC) at power-on, then the following startup procedure
for the CAN-device is recommended (example for node-ID=1):
a)
Send "NMT, Start remote node":
TX: ID=000, LEN=2, RTR=0, DATA=01 01
b)
Request the "Nodeguard Frame":
TX: ID=701, LEN=1, RTR=1
RX: ID=701, LEN=1, RTR=0, DATA=05/85 or 7F/FF
c)
If DATA=7F/FF (=> still PRE-OPERATIONAL, red ERROR-LED is ON)
- Repeat step
b)
40 times (=> red ERROR-LED goes OFF)
- Do step
a)
again (=> node starts successful now)