RackMounting
The SyncServer is designed for mounting in a standard 19-inch (48.26 cm) rack. Follow the
rack manufacturer's instructions for mounting the SyncServer.
Avoid the following conditions:
n
Elevated Operating Temperatures
: If the SyncServer is installed in a closed or multi-unit rack
assembly, the ambient temperature of the rack environment may be greater than the Syn-
cServer's Maximum Operating Temperature of 50°C/122°F. Install the SyncServer in an
environment that is compatible with the SyncServer's operating temperature range,
which is 0 °C to 50 °C, or 32 °F to 122 °F
n
Reduced Air Flow
: Position the SyncServer with enough space above, below, and adja-
cent to the chassis to allow an adequate flow of air so that it may operate safely.
Microsemi recommends leaving 1.4 in. (3.6 cm) above and below the SyncServer or
enough space to allow 5 CFM air flow.
n
Uneven Mechanical Loading
: Mount the equipment so as to avoid uneven mechanical load-
ing that could cause hazardous conditions.
n
Circuit Overloading:
Observe the power ratings on the SyncServer's nameplate and the
additional load the SyncServer may place on the supply circuit.
n
Proper Grounding:
Maintain reliable grounding (earthing) of rack-mounted equipment.
Groundingthe SyncServer
n
For VAC power, verify that a properly grounded three-prong outlet is available for the
standard power cord.
n
Connect the Chassis Grounding Screw on the rear panel to a reliable earth ground.
n
Verify that the equipment rack and other equipment are grounded correctly.
WARNING:Grounding
Microsemi recommends that the user connect the chassis grounding screw to a reliable
earth ground.
AVERTISSEMENT : Microsemi recommande que le châssis soit relié à une terre fiable.
ConnectingVACPower
For units equipped with the standard VAC power supply:
n
Verify that the power switch, located on the rear panel, is off. (Press "O".)
Page 98
..........................................................................
997-01520-02 Rev. G2
Summary of Contents for SyncServer S200
Page 2: ...Page 2...
Page 4: ......
Page 12: ......
Page 16: ......
Page 78: ......
Page 114: ......
Page 124: ......
Page 178: ......
Page 182: ...Glossary Page 182 997 01520 02 Rev G2...
Page 190: ......