Dinel, s.r.o. ULM–70
S T A R T I N G
Dinel
®
11 . OPERATION AND SETTING
Set the level meter using 3 buttons placed on the display module
(see Chapter Set-up elements). After 5 min. of inactivity, the level
meter automatically returns back to the measurement mode. If the
password is active, the level meter will be also locked. The val-
ues that have not been confirmed using the button
will not be
saved! After the meter is locked, you cannot change the setting!
When you attempt to edit, the words "NO PASSWORD" will appear
on the display. How to unlock the level meter is given on page 16.
After connection of the supply voltage to the level meter the display
shows the logo "Dinel" and the text "Starting" (approx. 15 s). Then,
the level meter goes to the measuring mode and the display shows
the current measured value.
11 .1 . BASIC CONFIGURATION
MIN LEVEL and MAX LEVEL
You can freely define the
minimum / maximum distance from the front surface of the
level meter
(item "LEVEL"for currents 4 / 20 mA). The "DISPLAY" is intended to set the value
displayed on the display. Setting the units is done in the "UNITS".
If in the bottom of the display appears (when entering the values) the inscription "OUT OF LIM
-
ITS", the value specified for the item "LEVEL" is outside the measuring range of the level meter.
If the inscription "SPAN TOO SMALL" is shown, it must be specified a larger span between Min
and Max values. For more information, see chapter "Specifications".
The decimal point position of the item 'LEVEL' is firmly set (according to the selected units), in
the item "DISPLAY" it is freely adjustable
After the first start of the level meter it is necessary to perform the
basic configuration (setting of the measuring range, choice of units
and possibly damping). The settings are accessible in the basic
menu by pressing
the "BASIC SETTINGS".
U N I T S
L E V E L :
m m
D I S P L A Y :
%
T E M P E R A T U R E
°C
M I N L E V E L
M A X L E V E L
U N I T S
D A M P I N G
S E N S I T I V I T Y
T E A C H I N G
M I N
ACTUAL LEVEL
0 2 8 7 0 m m
O U T P U T :
0 4 . 0 0 m A
L E V E L :
0 6 0 0 0
m m
D I S P L A Y :
0 0 0 0 0 %
M A X
ACTUAL LEVEL
0 2 8 7 0 m m
O U T P U T :
2 0 . 0 0 m A
L E V E L :
0 0 2 5 0
m m
D I S P L A Y :
0 0 1 0 0 %
ACTUAL LEVEL: Actual distance to
level
OUTPUT: current 4 mA / 20 mA
LEVEL: Definition of the min / max
level
DISPLAY: The value showed on the
display
M I N L E V E L
M A X L E V E L
U N I T S
D A M P I N G
S E N S I T I V I T Y
T E A C H I N G
B A S I C S E T T I N G S
S E R V I C E
D I A G N O S T I C
C L O N E S E T T I N G S
P A S S W O R D
L A N G U A G E
I N F O