background image

 

 

IM30-SA 

Doc. N° MO-0089-ING 

Rev. 

1

   FW: 

1.01

  

Pag. 

8   

of 

25

 

 

Copyright 2010 -  Microener

 

 

 

5. OUTPUT RELAYS 

 

Five output relays are available (R1, R2, R3, R4, R5) 

 

 

The relays 

R1,R2,R3,R4

 are normally deenergized (energised on trip): these output relays are user 

programmable and any of them can be associated to one of the IM30-SA's functions. 
One relay eventually associated to the instantaneous element of one of the functions, after pick-up 
normally drops-out  as soon as the tripping cause disappears (current below the set trip level). 
If the current remains above the trip level longer than the time delay programmed for the relevant 
function, the drop-out of the instantaneous relay is anyhow forced after an adjustable waiting time 
[tBO].(Diasactivation of the blocking output eventually used to block a relay upstream in the 
distribution system). 
Moreover any of the relays R1,R2,R3,R4, can be programmed to be energised at the end of the 
delay tBF(Breaker Failure function) 
Reset of the output relays associated to any time delayed function can be programmed to take 
place “Automatically” (tFRes= A) as soon as the tripping cause has disappeared, or “Manually”  
(tFRes= M) only by operating the ENTER/RESET key on re

lay’s front or via the serial bus. 

It has to be remarked that the programming structure does not allow to associate the same relay at 
the same time to  instantaneous and delayed elements. Therefore any relay already associated to 
any time delayed element cannot be associated to any instantaneous element and viceversa. 

 

 

The relay 

R5

, normally energised, is not programmable and it is deenergized on: 

 

 

internal fault 

 

 

power supply failure 

 

 

during the programming 

 

6. SERIAL COMMUNICATION  

 

The relays fitted with the serial communication option can be connected via a cable bus a fiber optic bus 
for interfacing with a Personal Computer (type IBM or compatible). 
All the functionalities that can be operated locally (for example reading of input measurement and 
changi

ng of relay’s settings) are also possible via the serial communication interface. 

Furthermore the serial port allows the user to read event recording and stored data. 
The unit has a RS232 / RS485 interface and can be connected either directly to a P.C. via a dedicated 
cable or to a RS485 serial bus, allowing having many relays to exchange data with a single master P.C. 
using the same physical serial line. A RS485/232 converter is available on request. 
The communication protocol is MODBUS RTU (only functions 3, 4 and 16 are implemented).  
Each relay is identified by its programmable address code (NodeAd) and can be called from the P.C.  
A dedicated communication software (MSCOM) for Windows 95/98/NT4 SP3 (or later) is available.   
Please refer to the MSCOM instruction manual for more information Microelettrica Scientifica. 

Summary of Contents for IM30-SA

Page 1: ...ROPROCESSOR OVERCURRENT AND EARTH FAULT PROTECTION RELAY TYPE IM30 SA OPERATION MANUAL MULTIFUNCTION 3ph O C E F Sensitive E F Neg Seq O C RELAY TYPE IM30 SA MODE SELECT I I Io Io PROG I R F S E F I2...

Page 2: ...____________________________ 11 10 1 ACT MEAS Actual measure _________________________________________________________ 11 10 2 MAX VAL Max values ______________________________________________________...

Page 3: ...t be compatible with their declared performance 1 6 PROTECTION EARTHING When earthing is required carefully check its efficiency 1 7 SETTING AND CALIBRATION Carefully check the proper setting of the d...

Page 4: ...n strict conformity with the safety regulations 1 11 FAULT DETECTION AND REPAIR Internal calibrations and components should not be alterated or replaced For repair please ask the Manufacturer or its a...

Page 5: ...er A B a K IEC A Inverse A 0 14 0 0 02 0 3366 IEC B Very Inverse B 13 5 0 1 0 6667 IEC C Extr Inverse C 80 0 2 1 2375 IEEE Moderate Inverse MI 0 0104 0 0226 0 02 4 1106 IEEE Short Inverse SI 0 00342 0...

Page 6: ...anning by the key SELECT Parameter modification by the key Set validation by the key ENTER Scanning of the menus by the key MODE SELECT ENTER Enabled only if input current is zero ENTER RESET MODE SEL...

Page 7: ...rip after expiry of the set trip time delay tI g Red LED I2 Flashing when measured current overcomes the set trip level I Illuminated on trip after expiry of the set trip time delay tI h Yellow LED BL...

Page 8: ...not allow to associate the same relay at the same time to instantaneous and delayed elements Therefore any relay already associated to any time delayed element cannot be associated to any instantaneo...

Page 9: ...al time 2tBF tBf 2tBO tBo 2tBO By proper interconnection of the blocking inputs and outputs of different relays it is possible to configurate very efficient arrangements of logic fault discrimination...

Page 10: ...the memory SET DISP Reading of the settings and of the configuration of the output relays as programmed PROG Access to the programming of the settings and of relay configuration TEST PROG Access to th...

Page 11: ...phase A displayed as primary Amps 0 99999 IBxxxxxA As above phase B ICxxxxxA As above phase C IoxxxxxA As above earth fault current I2xxxxxIn Negative Sequence component of the 3 phase current system...

Page 12: ...xxxxIn Current of phase A value recorded at the moment of tipping IBxxxxIn Current of phase B as above ICxxxxIn Current of phase C as above IoxxxxOn Earth fault current as above I2xxxxxIn Negative Seq...

Page 13: ...out relay R5 is deenergized Enter MODE PROG and SELECT either SETTINGS for programming of parameters or F RELAY for programming of output relays configuration enable programming by the indirect operat...

Page 14: ...s O 0 02On Trip level of high set earth fault element p u of the rated current of the C Ts for zero sequence detection 0 02 4 Dis 0 01 On tO 0 05s Trip time delay of the high set earth fault element 0...

Page 15: ...4 So 4 Instantaneous element of Sensitive earth fault element operates relay R1 R2 R3 R4 tSo 2 As above time delayed element operates relay R1 R2 R3 R4 I2 3 Instantaneous element of Negative Sequence...

Page 16: ...est environment or after all dangerous output connections are removed 14 MAINTENANCE No maintenance is required Periodically a functional check out can be made with the test procedures described under...

Page 17: ...d IEC61000 4 10 100A m 0 1 1MHz Electrical fast transient burst IEC61000 4 4 level 3 2kV 5kHz HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1 class 3 400pps 2 5kV m c 1k...

Page 18: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 18 of 25 Copyright 2010 Microener 17 CONNECTION DIAGRAM STANDARD OUTPUT SCE1575 Rev 0 17 1 CONNECTION DIAGRAM DOUBLE OUTPUT SCE1576 Rev 0...

Page 19: ...g 19 of 25 Copyright 2010 Microener 18 WIRING THE SERIAL COMMUNICATION BUS SCE1309 Rev 0 19 CHANGE PHASE CURRENT RATED INPUT 1 OR 5A J1 Phase A J2 Phase B J3 Phase C Rated Input Current Rated Input Cu...

Page 20: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 20 of 25 Copyright 2010 Microener 20 TIME CURRENT CURVES IEC TU0353 Rev 0 1 2...

Page 21: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 21 of 25 Copyright 2010 Microener 21 TIME CURRENT CURVES IEEE TU0353 Rev 0 2 2...

Page 22: ...ion of the screws driver mark Draw out the PCB by pulling on the handle 22 2 PLUG IN Rotate clockwise the screws and in the horizontal position of the screws driver mark Slide in the card on the rails...

Page 23: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 23 of 25 Copyright 2010 Microener 23 OVERALL DIMENSIONS PANEL CUT OUT 113x142 LxH View of Rear Terminal Connection...

Page 24: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 24 of 25 Copyright 2010 Microener 24 KEYBOARD OPERATIONAL DIAGRAM...

Page 25: ...earth fault 0 01 0 05 Dis On 0 05 tSo Time delay of sensitive earth fault 0 01 30 s 0 05 F I2 Operation characteristic of the Negative Sequence element D A B C MI SI VI I EI D I2 Tap of the negative...

Reviews: