background image

 

 

IM30-SA 

Doc. N° MO-0089-ING 

Rev. 

1

   FW: 

1.01

  

Pag. 

13  

of 

25

 

 

Copyright 2010 -  Microener

 

 

 

11. READING OF PROGRAMMED SETTINGS AND RELAY'S CONFIGURATION 

 

Enter the mode "SET DISP", select the menu "SETTINGS" or "F

RELAY", scroll information  

available in the menu by keys "+" or "-". 
SETTINGS= values of relay's operation parameters as programmed  
F

RELAY= output relays associated to the different functions as programmed.

 

 

12. PROGRAMMING 

 

The relay is supplied with the standard default programming used for factory test. [ Values here below 
reported 

( ----- ) 

]. 

All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP 

Local Programming by the front face key board is enabled only if no input current is detected 
(main switch open). Programming via the serial port is always enabled but a password is 
required to access the programming mode. The default password is the null string; in the 
standard appl

ication program for communication “MS-COM” it is also provided an emergency 

which can be disclosed on request only. 

As soon as programming is enabled, the Led  PRG/IRF flashes and the reclosing lock-out relay  R5 is 
deenergized. 
Enter  MODE   "PROG" and  SELECT either "SETTINGS" for programming of parameters or  
"F

RELAY" for programming of output relays configuration; enable programming by the indirect 

operation key PROG. 
The key SELECT now scrolls the available parameters. By the key  (+) , (-)  the displayed values can be 
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.    
Press key "ENTER/RESET" to validate the set values. 

 

12.1 - PROGRAMMING OF FUNCTIONS SETTINGS 

 

Mode PROG menu SETTINGS.  (Production standard settings here under shown). 

 

Display 

Description 

Setting Range 

Step 

Unit 

Fn

 50 

Hz

 

Mains frequency 

50 - 60  

10 

Hz 

In

 500

Ap

 

Rated primary current of the phase C.Ts. 

1 - 9999 

On

 500

Ap

 

Rated primary current of the C.Ts. or of the tore C.T. supplying the 
zero sequence current 

1 - 9999 

F(I>)

    D 

Operation characteristic of the low-set overcurrent element: 
(D)  

=  Independent definite time 

(A)  

=  IEC Inverse Curve type A 

(B)  

=  IEC Very Inverse Curve type B 

(C)  

=  IEC Extremely Inverse Curve type C 

(MI)  

=  IEEE Moderate Inverse Curve 

(SI)  

=  IEEE Short Inverse Curve 

(VI)  

=  IEEE Very Inverse Curve 

(I)  

=  IEEE Inverse Curve 

(EI)  

=  IEEE Extremely Inverse Curve 




MI 

SI 
VI 

EI 




MI 

SI 
VI 

EI 

In

  500  

Ap

 

Ap

 is the unit of measure, 

Amps primary.

 

500

 is the 

setting default 

In 

is the name 

of the variable

 

Summary of Contents for IM30-SA

Page 1: ...ROPROCESSOR OVERCURRENT AND EARTH FAULT PROTECTION RELAY TYPE IM30 SA OPERATION MANUAL MULTIFUNCTION 3ph O C E F Sensitive E F Neg Seq O C RELAY TYPE IM30 SA MODE SELECT I I Io Io PROG I R F S E F I2...

Page 2: ...____________________________ 11 10 1 ACT MEAS Actual measure _________________________________________________________ 11 10 2 MAX VAL Max values ______________________________________________________...

Page 3: ...t be compatible with their declared performance 1 6 PROTECTION EARTHING When earthing is required carefully check its efficiency 1 7 SETTING AND CALIBRATION Carefully check the proper setting of the d...

Page 4: ...n strict conformity with the safety regulations 1 11 FAULT DETECTION AND REPAIR Internal calibrations and components should not be alterated or replaced For repair please ask the Manufacturer or its a...

Page 5: ...er A B a K IEC A Inverse A 0 14 0 0 02 0 3366 IEC B Very Inverse B 13 5 0 1 0 6667 IEC C Extr Inverse C 80 0 2 1 2375 IEEE Moderate Inverse MI 0 0104 0 0226 0 02 4 1106 IEEE Short Inverse SI 0 00342 0...

Page 6: ...anning by the key SELECT Parameter modification by the key Set validation by the key ENTER Scanning of the menus by the key MODE SELECT ENTER Enabled only if input current is zero ENTER RESET MODE SEL...

Page 7: ...rip after expiry of the set trip time delay tI g Red LED I2 Flashing when measured current overcomes the set trip level I Illuminated on trip after expiry of the set trip time delay tI h Yellow LED BL...

Page 8: ...not allow to associate the same relay at the same time to instantaneous and delayed elements Therefore any relay already associated to any time delayed element cannot be associated to any instantaneo...

Page 9: ...al time 2tBF tBf 2tBO tBo 2tBO By proper interconnection of the blocking inputs and outputs of different relays it is possible to configurate very efficient arrangements of logic fault discrimination...

Page 10: ...the memory SET DISP Reading of the settings and of the configuration of the output relays as programmed PROG Access to the programming of the settings and of relay configuration TEST PROG Access to th...

Page 11: ...phase A displayed as primary Amps 0 99999 IBxxxxxA As above phase B ICxxxxxA As above phase C IoxxxxxA As above earth fault current I2xxxxxIn Negative Sequence component of the 3 phase current system...

Page 12: ...xxxxIn Current of phase A value recorded at the moment of tipping IBxxxxIn Current of phase B as above ICxxxxIn Current of phase C as above IoxxxxOn Earth fault current as above I2xxxxxIn Negative Seq...

Page 13: ...out relay R5 is deenergized Enter MODE PROG and SELECT either SETTINGS for programming of parameters or F RELAY for programming of output relays configuration enable programming by the indirect operat...

Page 14: ...s O 0 02On Trip level of high set earth fault element p u of the rated current of the C Ts for zero sequence detection 0 02 4 Dis 0 01 On tO 0 05s Trip time delay of the high set earth fault element 0...

Page 15: ...4 So 4 Instantaneous element of Sensitive earth fault element operates relay R1 R2 R3 R4 tSo 2 As above time delayed element operates relay R1 R2 R3 R4 I2 3 Instantaneous element of Negative Sequence...

Page 16: ...est environment or after all dangerous output connections are removed 14 MAINTENANCE No maintenance is required Periodically a functional check out can be made with the test procedures described under...

Page 17: ...d IEC61000 4 10 100A m 0 1 1MHz Electrical fast transient burst IEC61000 4 4 level 3 2kV 5kHz HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1 class 3 400pps 2 5kV m c 1k...

Page 18: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 18 of 25 Copyright 2010 Microener 17 CONNECTION DIAGRAM STANDARD OUTPUT SCE1575 Rev 0 17 1 CONNECTION DIAGRAM DOUBLE OUTPUT SCE1576 Rev 0...

Page 19: ...g 19 of 25 Copyright 2010 Microener 18 WIRING THE SERIAL COMMUNICATION BUS SCE1309 Rev 0 19 CHANGE PHASE CURRENT RATED INPUT 1 OR 5A J1 Phase A J2 Phase B J3 Phase C Rated Input Current Rated Input Cu...

Page 20: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 20 of 25 Copyright 2010 Microener 20 TIME CURRENT CURVES IEC TU0353 Rev 0 1 2...

Page 21: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 21 of 25 Copyright 2010 Microener 21 TIME CURRENT CURVES IEEE TU0353 Rev 0 2 2...

Page 22: ...ion of the screws driver mark Draw out the PCB by pulling on the handle 22 2 PLUG IN Rotate clockwise the screws and in the horizontal position of the screws driver mark Slide in the card on the rails...

Page 23: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 23 of 25 Copyright 2010 Microener 23 OVERALL DIMENSIONS PANEL CUT OUT 113x142 LxH View of Rear Terminal Connection...

Page 24: ...IM30 SA Doc N MO 0089 ING Rev 1 FW 1 01 Pag 24 of 25 Copyright 2010 Microener 24 KEYBOARD OPERATIONAL DIAGRAM...

Page 25: ...earth fault 0 01 0 05 Dis On 0 05 tSo Time delay of sensitive earth fault 0 01 30 s 0 05 F I2 Operation characteristic of the Negative Sequence element D A B C MI SI VI I EI D I2 Tap of the negative...

Reviews: