4. SIGNALIZATIONS
Eight signal leds (normally off) are provided:
a) Red LED
I>
Flashing when measured current overcomes the set trip level [I>].
Illuminated on trip after expiry of the set trip time delay [tI>].
b) Red LED
I>>
Same as above related to [I>>], [tI>>].
c) Red LED
Io>
Same as above related to [O>], [tO>].
d) Red LED
Io>>
Same, as above related to [O>>], [tO>>].
e) Yellow LED
PROGRAM/
BLOCK FAIL
Flashing during the programming of the parameters or in case
Illuminated on Internal Relay Fault.
f) Red LED
S.E.F.
Flashing when measured current overcomes the set trip level [I>].
Illuminated on trip after expiry of the set trip time delay [tI>].
g) Red LED
I2>
Flashing when measured current overcomes the set trip level [I>].
Illuminated on trip after expiry of the set trip time delay [tI>].
h) Yellow LED
BLOCK ACTIVE
BRKR FAIL
Flashing when a blocking signal is present at the relevant input
terminals.
Lit-on when the BREAKER FAILURE function is activated.
The reset of the leds takes place as follows:
Leds
a,b,c,d,g
From flashing to off, automatically when the lit-on cause disappears.
From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
Leds
e,f,h
From ON to OFF, automatically when the lit-on cause disappears.
In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power
supply is restored.
I>
I>>
Io>
Io>>
BLOCK ACTIVE
BRKR FAIL
PROG/
S.E.F.
I
2
>
I.R.F.
a
b
c
d
e
f
g
h