24. SETTING’S FORM
Relay Type
IM30-CV
Station :
Circuit :
Date :
/
/
Firmware Version:
Relay Serial Number :
Power Supply
24V(-20%) / 110V(+15%) a.c.
24V(-20%) / 125V(+20%) d.c.
Rated Current :
80V(-20%) / 220V(+15%) a.c.
90V(-20%) / 250V(+20%) d.c.
RELAY PROGRAMMING
Variable
Description
Setting
Range
Default
Setting
Actual
Setting
Test Result
Pick-up Reset
Fn
Mains frequency
50 - 60
Hz
50
In
Rated primary current of the phase C.Ts.
0 - 9999
Ap
500
Un
Rated secondary voltage of the P.Ts.
50 - 125
V
100
F(IL)
Operation characteristic of the low-set overcurrent element
D - SI
-
D
IL
Trip level of low-set overcurrent element
0.3-1.5-Dis
In
0.3
tIL
Trip time delay of the low-set overcurrent element
1 - 50
s
1
IH
Trip level of high-set overcurrent element
0.2 - 2 - Dis
In
0.6
tIH
Trip time delay of the high-set overcurrent element
0.1
– 6500
s
0.1
F(OL)
Operation characteristic of the low-set earth fault element
D - SI
-
D
OL
Trip level of low-set earth fault element
0.1-1.0-Dis
In
0.1
tOL
Trip time delay of low-set earth fault element
0.05
– 30
s
0.05
OH
Trip level of high-set earth fault element
0.1-2.0-Dis
In
0.2
tOH
Trip time delay of the high-set earth fault element
0.05
– 9.99
s
0.05
F(UL)
Operation characteristic of the low-set unbalance element
D - SI
-
D
UL
Trip level of low-set unbalance element
0.02-0.8-Dis
Un
0.02
tUL
Trip time delay of low-set unbalance element
1.0 - 30
s
1.0
UH
Trip level of high-set unbalance element
0.01-1.0-Dis
Un
0.04
tUH
Trip time delay of the high-set unbalance element
0.1 - 300
s
1
I<
Trip level of undercurrent element
Dis-0.10-1.0
In
0.1
tI<
Trip time delay of the undercurrent element
1.0
– 99.9
s
1
tRI<
Wait time for the reenergization of the capacitors
Dis-0.5-100
m
5
Uc
Unbalance compensation level
0.00 - 0.2
Un
.00
c
Uo
IA phase displacement
0 - 359
°
0
B14
C/B status monitoring input enabled/disabled
En - Dis
-
Dis
tBF
Max reset time delay of the instantaneous element
0.1-0.75
s
0.1
NodAd
Identification number for the serial connection
1 - 250
-
1
CONFIGURATION OF OUTPUT RELAYS
Default Setting
Actual Setting
Prot
Elem.
Output Relays
Description
Prot.
Elem.
Output Relays
IL
-
-
3
-
Instantaneous element of low-set overcurrent
IL
tIL
1
2
-
-
As above, time delayed element
tIL
IH
-
-
3
-
Instantaneous element of high-set overcurrent
IH
tIH
1
2
-
-
As above, time delayed element
tIH
OL
-
-
-
-
Instantaneous element of low-set earth fault element
OL
tOL
1
2
-
-
As above, time delayed element
tOL
OH
-
-
-
-
Instantaneous element of high-set earth fault element
OH
tOH
1
2
-
-
As above, time delayed element
tOH
UL
-
-
-
-
Instantaneous element of low-set unbalance element
UL
tUL
-
2
-
-
As above, time delayed element
tUL
UH
-
-
-
-
Instantaneous element of high-set unbalance element
UH
tUH
-
2
-
-
As above, time delayed element
tUH
tI<
-
-
-
4 Time delayed element min. current
tI<
tRI
-
-
-
-
Start of reclose timer tRI
tRI
tBF
-
-
-
Breaker failure element
tBF
tFRes
:
M
Relay reset mode A = Automatic, M = Manual
tFRes
:
Bf
-
-
-
i
The input for blocking the operation of the time delayed elements relevant to
phase faults (IL, IH, OL, OH)
Bf
Bo
-
u
The input for blocking the operation of the time delayed elements relevant to
unbalance (UH, UL)
Bo
tBf
2tBF
Breaker failure alarm
tBf
tBo
2tBF
As above for the unbalance functions
tBo
Commissioning Engineer :
Date :
Customer Witness :
Date :