IM30-CV
Doc. N° MO-0150-ING
Rev.
1
Date
14.07.2003
Copyright 2010 - Microener
Firmware:
1.0X
Pag
11
di
24
10.3 LASTTRIP
Display of the function which caused the last tripping of the relay plus values of the parameters at the
moment of tripping. The memory buffer is refreshed at each new relay tripping.
Display
Description
Cause
xxx
Display of the function which caused the last tripping:
IL; IH; OL; OH; UL; UH; I<
IA
xx.x
In
Current of phase A
IB
xx.x
In
Current of phase B
IC
xx.x
In
Current of phase C
Io
xx.x
In
Residual current (3 x Zero Sequence current)
Ud
x.xx
Un
Unbalance compensated voltage
10.4 TRIP NUM
Counters of the number of operations for each of th
e relay’s functions.
The memory is non-volatile and can be cancelled only with a secret procedure.
Display
Description
IL
xxxxxx
Low set overcurrent trips
IH
xxxxxx
High set overcurrent trips
OL
xxxxxx
Low set Earth Fault
OH
xxxxxx
High set Earth Fault
UL
xxxxxx
Low set unbalance
UH
xxxxxx
High set unbalance
I<
xxxxxx
Undercurrent trips
11. READING OF PROGRAMMED SETTINGS AND RELAY'S CONFIGURATION
Enter the mode "SET DISP", select the menu "SETTINGS" or "F
RELAY", scroll information
available in the menu by keys "+" or "-".
SETTINGS= values of relay's operation parameters as programmed
F
RELAY= output relays associated to the different functions as programmed.