12. PROGRAMMING
The relay is supplied with the standard default programming used for factory test. [ Values here below reported in
the “ Display “ column ].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Local Programming by the front face key board is enabled only if no input current is detected (main switch
open). Programming via the serial port is always enabled but a password is required to access the
programming mode. The default password is the null string; in the standard application program for
communication “MS-COM” it is also provided an emergency password which can be disclosed on request
only.
As soon as programming is enabled, the Led PRG/IRF flashes and the reclosing lock-out relay R5 is
deenergized..
Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters or
"F
RELAY" for programming of output relays configuration; enable programming by the indirect
operation key PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.
12.1 - PROGRAMMING OF FUNCTION SETTINGS
Mode PROG menu SETTINGS. (Production standard settings here under shown).
Display
Description
Setting Range
Step
Unit
Fn
50
Hz
Mains frequency
50 - 60
10
Hz
In
500
Ap
Rated primary current of the phase C.Ts.
0 - 9999
1
A
Un
100
V
Rated secondary voltage of the P.Ts. supplying the
unbalance voltage element .
50 - 125
0.1
V
F(IL)
D
Operation characteristic of the low-set overcurrent element
D =Independent definite time
SI = Dependent normal inverse time
D
SI
D
SI
-
IL
0.3
In
Trip level of low-set overcurrent element
(p.u. of the rated current of the phase C.Ts.)
0.3 - 1.5 - Dis
0.01
In
tIL
1
s
Trip time delay of the low-set overcurrent element
In the inverse time operation it is the trip time delay at
I = 10xI>
1 - 50
0.1
s
IH
0.6
In
Trip level of high-set overcurrent element
(p.u. of the rated current of the phase C.Ts.)
0.2 - 2 - Dis
0.01
In
tIH
0.1
s
Trip time delay of the high-set overcurrent element
0.1
– 6500
(0.1-99.9)
0.1
(100-6500)
1
s
Fn
50
Hz
Hz
is the unit of measure
50
is the
default setting
Fn
is the name
of the variable