MC2-30V
Doc. N°
MO-0499-ING
Copyright 2019
Date
17.03.2022
Rev.
2
Pag. 36
of
63
17.7 – Function:
2U>
(Second Overvoltage Element F59)
Status
→
Enab.
Yes
[No / Yes]
Oper. Levels
→
Us
90
%Un (10
÷
190)
step 1
Timers
→
ts
100
s
(0.08
÷
100)
step
0.01
17.7.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Us
: Minimum operation level
ts
: Trip time delay
17.7.2 - Operation
Tripping of the function operates a user programmable output relay.
17.8 - Function:
1U<
(First Undercurrent Element F27)
Status
→
Enab.
Yes
[No / Yes]
Oper. Levels
→
Us
90
%Un
(10
÷
190)
step 1
Timers
→
ts
100
s
(0.08
÷
100)
step
0.01
17.8.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Us
: Minimum operation level
ts
: Trip time delay
17.8.2 - Operation
Tripping of the function operates a user programmable output relay.
17.9 - Function:
2U<
(Second Undercurrent Element F27)
Status
→
Enab.
Yes
[No / Yes]
Oper. Levels
→
Us
90
%Un
(10
÷
190)
step 1
Timers
→
ts
100
s
(0.08
÷
100)
step
0.01
17.9.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Us
: Minimum operation level
ts
: Trip time delay
17.9.2 - Operation
Tripping of the function operates a user programmable output relay.