17.10 - Function:
1f>
(First Overfrequency Element F81>)
Status
→
Enab.
Yes
[No / Yes]
Oper. Levels
→
Fs
52
Hz
(40
÷
70)
step 0.01
Timers
→
ts
10
s
(0.1
÷
100)
step
0.01
17.10.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Fs
: Minimum operation level
ts
: Trip time delay
17.10.2 - Operation
Tripping of the function operates a user programmable output relay.
17.11 - Function:
2f>
(Second Overfrequency Element F81>)
Status
→
Enab.
Yes
[No / Yes]
Oper. Levels
→
Fs
52
Hz
(40
÷
70)
step 0.01
Timers
→
ts
10
s
(0.1
÷
100)
step
0.01
17.11.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Fs
: Minimum operation level
ts
: Trip time delay
17.11.2 - Operation
Tripping of the function operates a user programmable output relay.