17.18 - Function:
1df/dt
(First Frequency rate of change Element)
Status
→
Enab.
Yes
[No / Yes]
Options
→
Sfr
POS
(POS/NEG/POS-NEG)
Oper. Levels
→
df/dt
1
Hz/s
(0.1
÷
9.9)
step 0.1
→
Ub
30
%Un (30
÷
90)
step 1
17.18.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Sfr
: Rate of Change direction:
POS
Positive
NEG
Negative
POS-NEG
Positive and Negative
df/dt
: Minimum operation level
Ub
: Minimum voltage level
17.18.2 - Operation
Tripping of the function operates a user programmable output relay.
17.19 - Function:
2df/dt
(Second Frequency rate of change Element)
Status
→
Enab.
Yes
[No / Yes]
Options
→
Sfr
POS
(POS/NEG/POS-NEG)
Oper. Levels
→
df/dt
1
Hz/s
(0.1
÷
9.9)
step 0.1
→
Ub
30
%Un (30
÷
90)
step 1
17.19.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Sfr
: Rate of Change direction:
POS
Positive
NEG
Negative
POS-NEG
Positive and Negative
df/dt
: Minimum operation level
Ub
: Minimum voltage level
17.19.2 - Operation
Tripping of the function operates a user programmable output relay.