MC2-30V
Doc. N°
MO-0499-ING
Copyright 2019
Date
17.03.2022
Rev.
2
Pag. 46
of
63
17.22.5 – Example: Setting “Oscillo Trigger Logic”
Open software program and connect to the relay.
Select “
Change Windows
” from “
Menu
” button
Select “
User Variable
”
Setting for “
User Trigger Oscillo
” : “
1U>/2U>
”, “
AND
”, “
1
”, “
Monostable
”, “
10
”.
17.22.5.1 – “Linked Functions”
Select “
Linked Functions
” related to “User Trigger Oscillo” and press
right button on mouse, select “Value change”:
Select “
1U>, 2U>
” from “Available” box via push-button “<Add”, and press “OK”.
For remove functions, use push-button “>Remove”.