MC2-30M
Doc. N°
MO-0495-ING
Copyright 2018
Date
17.03.2022
Rev.
2
Pag. 40
of
64
17.12 - Function:
3Io>
(Third Earth Fault Element 50N/51N)
Status
→
Enab.
Yes
[No / Yes]
Options
→
tBI
Off
[Off / 2tBO]
Oper.Levels
→
Is
0.01
On
(0.01
÷
9.99)
step 0.01 On
Timers
→
ts
100
s
(0.02
÷
100)
step
0.01 s
→
tBO
0.75
s
(0.05
÷
0.75)
step
0.01 s
On = Rated primary current of CTs or of the current Tore CT.
17.12.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
tBI
: Blocking Input reset time
Off
= Permanent block
2tBO
= Set 2xtBO.
Is
: Minimum operation level
ts
: Trip time delay
tBO
: Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
also the trip time delay of the Breaker Failure function.