17.18 - Function:
StSeq
(starting Sequence Control)
Status
→
Enab.
Yes
[No / Yes]
Oper.Levels
→
ITr
10
In
(0.1
÷
1)
step
0.1
In
Timers
→
tTr
20
s
(0.5
÷
50)
step
0.1
s
17.18.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
Itr
: Switch-over current of motor starter
tstNo
: Trip time delay of LR during run
17.18.2 - Operation
During start-up of the motor, the unit can control an output relay used to operate the switch-over of motor
starter (star-delta, resistance or impedance, autotransformer, etc...) thus allowing to automatically manage
the starting transition by controlling the parameters “ITr”, “tTr”.
At motor start counting of “tTr” begins. If during “tTr” the motor current drops below “lTr”, switching-over is
operated; if motor current stays above “lTr” longer than “tTr”, the Locked Rotor element is activated.
17.19 - Function:
I<
(No load running)
Status
→
Enab.
No
[No / Yes]
Oper.Levels
→
I<
0.5
In
(0.15
÷
1)
step 0.01 In
Timers
→
tI<
30
s
(0.1
÷
90)
step
0.01 s
17.19.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
I<
: Operation level
tI<
: Trip time delay
17.19.2 - Operation
This function performs the protection against no-load running: it is activated by motor under current.