18.3 – Physical Outputs
The output relay are fully user programmable and controlled by any protection functions and by any digital
inputs.
0.R1
Programmable (R1)
Available in the relay
0.R2
Programmable (R2)
0.R3
Programmable (R3)
0.R4
Programmable (R4)
0.R5
Programmable (R5)
0.R6
Programmable (R6)
0.R7
Programmable (R7)
0.R8
Programmable (R8)
18.4 - “DO” Configuration
Any Output Relay can be programmed to be controlled (energized) by one or more of the following functions
or Digital Inputs:
18.4.1 - Example configuration
18.4.1.1 - Relay
Relay internal name
18.4.1.2 - Linked function
It’s available only 1 link, select the function for tripping the output relay (for multiple association use
“User Variable”)
18.4.1.3 - Operation Logic
Not Used
18.4.1.4 - Logical Status
Relay Logical status
18.4.1.5 - Output Configuration
Normally Denergized
The output relay is denergized in normal conditions and gets energized on
activation of the controlling Functional Output; reset means denergizing.
Normally Energized
The output relay is energized in normal conditions and gets denergized on
activation of the controlling Functional Output; reset means energizing.
18.4.1.6 - tON (Operation Time)
This timer controls the duration of the activation of the output relay.
tON
:
0
(0.01-10)s, step 0.01s
18.4.1.7 - Relay Status
Relay – Physical status