![MicroControl uCAN.8.dio-BOX Manual Download Page 53](http://html1.mh-extra.com/html/microcontrol/ucan-8-dio-box/ucan-8-dio-box_manual_1786185053.webp)
CANopen Protocol
Object Dictionary
Page
53
MicroControl Version 2.00
μCAN.8.dio-BOX
8
Digital Input Value
Index 6000h
By a read operation of index 6000h the state of the digital inputs
can be retrieved.
Sub-Index
Data Type
Acc.
Name
Default Value
0
Unsigned8
ro
Largest Sub-Index
01h
1
Unsigned8
ro
Read Input 8-Bit
-
The object is read-only. Only sub-indices 0 and 1 are supported.
An access to other sub-indices will lead to an error message.
Beispiel:
read digital inputs
ID
DLC
B0
B1
B2
B3
B4
B5
B6
B7
601h
8
40h
00h
60h
01h
00h
00h
00h
00h
, module address = 1
As response the μCAN.8.dio-BOX will send:
ID
DLC
B0
B1
B2
B3
B4
B5
B6
B7
581h
8
42h
00h
60h
01h
01h
00h
00h
00h
In this example the digital input 1 has a high level, all other in-
puts have a low leveI.
Input Polarity
Index 6002h
With the object at index 6002h the polarity of the digital inputs
can be changed..
Sub-Index
Data Type
Acc.
Name
Default Value
0
Unsigned8
ro
Largest Sub-Index
01h
1
Unsigned8
rw
Polarity Input 8-Bit
00h
Only sub-indices 0 and 1 are supported. An access to other sub-