Installation EMC
Considerations
Page
23
MicroControl Version 2.00
μCAN.8.dio-BOX
5
5.2.3 CAN Cable
The CAN cable must meet the requirements of ISO11898. The
cable must meet the following specifications:
Tabelle 2: Specifications of CAN bus cable
Parameter
Value
Impedance
108 - 132 Ohm (nom. 120 Ohm)
Specific Resistance
70 mOhm/Meter
Specific Signal Delay
5 ns/Meter
The CAN bus cable is connected to the µCAN.8.dio-BOX module
via terminals inside the case. For the pinning of the terminal refer
to “CAN Bus” on page 26 of this manual.
Do not confuse the signal lines of the CAN bus, otherwise com-
munication
Attention !
between the modules is impossible. The shield of the
CAN bus cable may never lead inside the µCAN case. Never
connect the shield to one of the terminals inside the case.