37
SETUP MENU SETTINGS
AC RUN TO
XX.XV
TRANSFER SWITCH
X
11.7 AC Run To Voltage
“This setting only applies for Solar Control Mode”
This allows the user to set the level the solar regulator will
charge the battery to before the inverter switches back to battery power.
Press
to change the AC Run To Voltage,
The AC Run To
settings can be changed as follows:
AC Run to Settings
Table 11-3:
Table 11-4:
Lead Acid
AC Run to Voltage settings
Lithium
AC Run to Voltage Settings
To change the Menu, press
, the menu changes to Transfer Switch Time
11.8 Transfer Switch Time
To change the
Transfer Switch Time
settings press
.
The inverter uses a transfer relay to switch between the Grid and Inverter Mode.
The transfer time can be changed. In most applications the default vale will suffice.
For applications where Servers, Desktop Computers, DSTV are connected to the inverter,
change the transfer time to “5ms - No Softstart”.
The Menu settings can be changed as follows
Table 11-5: System Setup - Transfer Switch time settings
3ms - No Softstart
3 milli second transfer time and will restart load instantly - with
mains fail prediction.
5ms
– No Softstart
5 milli second transfer time and will restart load instantly - with
mains fail prediction.
8ms - Softstart*
(Default) 8 milli second transfer time and will ramp the RMS
voltage up in less than 1 second - with mains fail prediction.
Default Setting
Gen - Softstart
8 milli second transfer time and will ramp the RMS voltage up in
less than 1 second - with
no
mains fail prediction.
Gen - Slow Ramp
8 milli second transfer time and will ramp the RMS voltage up in
3 seconds - with
no
mains fail prediction.
To change the Menu, press
, the menu changes to Load Monitoring
48 V System
50
51
52
52.5
53
53.5
Default Lead Acid
54
48V System
50.8
51.4
Default Lithium
51.8
52.6
53.4
53.8
55