BATTERY SETUP SETTINGS
BOOST TIME
X
FLOAT
XX.XV
10.7 Battery Float Voltage
To change the
BATTERY FLOAT VOLTAGE
settings, Press
This allows the user to adjust the
BATTERY FLOAT
voltage.
The float settings can be changed as follows:
10.7.1 Battery Float Voltage Settings
Table 10-3a: Battery Setup - Battery Float Voltage Firmware V21R1
48V System
51.6
Default
– Lithium
52.8
53.6
54
Default - Lead Acid
55.2
“Please consult your battery supplier for the correct battery charging specifications.
To change the Menu press
, the menu changes to Battery Boost Time
10.8 Battery Boost Time
To change the
BATTERY BOOST TIME
settings, Press
This allows the user to select the
TIME duration
that the
BOOST VOLTAGE
will be held at before
changing to FLOAT.
By Pressing
you can select 1 min, 30min, 1, 2 or 3 hours.
Lead Acid Default = 2hrs.
Lithium-Ion Default = 1 min.
“Please consult your battery supplier for the correct battery charging specifications.
To change the Menu press
, the menu changes to Battery Low Off At