Micro-Air, Inc.
Page 23
EasyTouch 2.5 Operations Manual
Rev 1.0 8/27/14
Figure 14
– DX Operational Settings Menu Screens
Refer to Table 3 for a quick reference to the DX Operational Settings. Refer to the sections that
follow for further details on each setting.
Table 3
– DX Operational Settings
No.
Page Description
Factory
Default
Parameter Range
1
1
Compressor Start Delay
15 sec
5
– 135 sec
2
Failsafe Level
Faults
Detected
and
Displayed
with
Lockout
Faults Not Detected /
Faults Detected But Not
Displayed /
Faults Detected and
Displayed /
Faults Detected and
Displayed with Lockout
3
Low-Voltage Monitor
Off
Off/75-120VAC or
Off/175-240VAC
4
2
De-Ice Cycle
Enabled
with
5°F/3°C
Sensor
Differential
Disabled
Enabled with 5°F/3°C
Sensor Differential
Enabled with 7°F/4°C
Sensor Differential
5
Pump Sentry
Off
Off / 100-150°F or
Off / 40-65°C
6
Pump Operate Mode
Continuous Continuous or Cycled
7
3
Low Pressure Detection
Set by
Jumper
Set by Jumper or
Disabled
11.2.1 Compressor Start Delay (5-135sec;
15sec
)
The compressor start delay is used for installations where more than one system operates
from the same power source. Setting different start delays allows compressors to start at
different times when AC power is interrupted. Stage the units at least 5 seconds apart. Note
that this delay is only applied immediately after an AC power up and will only affect the first
cooling or heating cycle that is called for, assuming the EasyTouch powers up in the ON
mode. All subsequent cooling or heating cycles begin upon demand per the normal
sequence.
11.2.2 Failsafe Level (Faults Not Detected / Faults Detected But Not Displayed / Faults Detected
and Displayed / Faults Detected and Displayed with Lockout;
Faults Detected
and Displayed with Lockout
)
This parameter controls the display and response to the various fault conditions. To protect
the air conditioning equipment, certain fault conditions trigger a Lockout. A Lockout occurs
when the control shuts down and will not automatically restart until the power (button) on the
display is cycled. The detection and the display of faults are also controlled by this parameter.