SECTION E: For Operators with Interface Modules or Logic boards
Installation Safety Precautions
WARNING: MICANAN MK00649 NEMA-1, MK00650 NEMA-4 and FRABA MK00697 NEMA 4/4X infrared photo
systems are for use only with MICANAN logic board operators or relay logic operators equipped with the Micanan
failsafe interface module. Use of this device on other than recommended operators can lead to severe or fatal injury.
Follow these instructions carefully.
IMPORTANT:
For momentary activation on close, the MICANAN photobeams (or a Micanan 2-wire monitored edge),
must be installed as part of the operator system.
If a Micanan 2-wire monitored edge or the MICANAN infrared
photobeam system is not installed (or not operating correctly), the operator will only operate in fault mode (constant
pressure to close).
READ and FOLLOW all installation instructions.
1.
Before installing the photo beam, read the door or gate operator’s instruction manual fully, so you are aware of all of the
unit’s functions and features.
2.
Wear protective gloves and eye protection when using tools.
3.
Before installing photo beam, disconnect all power to door operator to prevent unintended operation and have the door full
open or close.
4.
Do not reconnect power to the door or gate operator until instructed to do so.
5.
Only install photobeams on a properly functioning door or gate operator.
6.
Installation and wiring must comply with local building and electrical codes. This device is not intended and must not be
installed in an explosive environment.
WARNING: Keep fingers and other body parts away from all moving parts of the door and gate operator system while
the system is being operated.
WARNING: To prevent unintended operation, disconnect power to the door or gate operator prior to installing the
photobeam system.
MICANAN N-1 PHOTOCELL (MK00649)
Note: The MK00649 photocell system has a maximum range of 24 ft. Sun visor protector optional.
Installation
Note: Photo beams should be mounted as close to the door track inside the door to offer maximum entrapment
protection.
Wall installation:
1.
Select a location on the wall no more than 6 inches from the floor to install wall mounting brackets on the left and right
side of the door. Both brackets must be mounted at the same height for proper alignment.
2.
Drill holes in the wall and attach brackets to the wall using screws and nails provided as shown in Fig. 1.
INSTALLATION OF MICANAN N-1 OR N-4 PHOTOCELLS
Summary of Contents for PRO-LH
Page 1: ...For more information please visit www devancocanada com or call toll free at 855 931 3334...
Page 2: ......
Page 15: ......
Page 16: ......
Page 17: ...1 7...
Page 18: ...1 8...
Page 21: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......