6) Connect safety devices
Failsafe feature: A monitored failsafe safety feature is built into the operator. The operator has provisions to connect one
primary monitored safety device as well as one or more non-monitored safety device(s).
Primary monitored safety device:
MICANAN monitored failsafe photo beams or MICANAN compatible monitored failsafe devices must be connected to
terminals P1 and P2 if momentary close on pushbutton is required (B2 mode). If not connected, door can only be closed by
constant pressure on close pushbutton. If constant pressure on close pushbutton is removed before door reaches full closed
position, then door reverses to full open.
Note: Only one monitored failsafe safety device can be connected across terminals P1 and P2.
Note: See section E for complete installation instructions for the Micanan N-1 or N-4 photocells or the FRABA photocells.
Secondary non-monitored safety device(s):
A standard 2-wire safety edge, non-monitored reflective or thru-beam photo eye or any other non-monitored reversing devices
with a N.O dry contact can be connected to terminals S1 and S2.
Note: More than one secondary non-monitored safety device can be connected to terminals S1 and S2.
Important: Do not remove resistor that is factory installed across terminals S1 and S2 unless installing a 4-wire electric edge.
4-wire electric edge Connection
A standard 4-wire electric edge can be connected across S1 and S2 terminals as a secondary safety device. Remove the factory
installed resistor across terminals S1 and S2 and install resistor across the black and white pair of wires from the electric edge
and connect the remaining black and white wire to the S1 and S2 terminals.
7) Select Mode of Operation:
C2
mode of operation (momentary on open, constant pressure on close):
The operator is wired at the factory for momentary on open and constant pressure on close. For single phase limited duty
operators, the purple wire is left unconnected. For 3-phase (1/2HP 380V 50Hz) operators, white wire is connected to terminal
T6.
B2
mode of operation (momentary on open, momentary on close):
If momentary on close is required: For single phase limited duty operators, connect purple wire to terminal #5. For 3-phase
(1/2HP 380V 50Hz) operators, remove the white wire from terminal T6 and place it on terminal T3.
The operator functions in B2 mode only when the primary monitored safety device is connected and functioning properly. If it is
not connected, operator will go into fault mode and door can only be closed by constant pressure on close and if constant
pressure on close is removed before door reaches full close position, door reverses to full open.
Summary of Contents for PRO-LH
Page 1: ...For more information please visit www devancocanada com or call toll free at 855 931 3334...
Page 2: ......
Page 15: ......
Page 16: ......
Page 17: ...1 7...
Page 18: ...1 8...
Page 21: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......