Heating circuit water quality
Heating circuit water quality
The composition and quality of the
system water have a direct influence on
the performance of the whole system
and the life of the boiler. On first filling,
and any subsequent refilling, a pH
balance of 7-8 should be maintained.
Please see the table below
The system must be flushed, cleansed
and treated with a good quality
corrosion inhibitor suitable for all the
materials in the system before the
boiler is put into use
.
Failure to do this may affect the
boilers warranty.
No Chemical anti-corrosion medium
should be introduced to the system
Recommended Water treatment
Specialists:
Fernox
Forsyth Road
Sheerwater
Woking
Surrey
GU21 5RZ
www.fernox.com
Office Tel: 01483 793200
Technical Support: 0870 870 0362
Criterion
Appropriate Value
Effect of Deviation
PH - balance
7 - 8
Danger of corrosion for boiler and system
components.
Hardness
1 4 d H
-
Raised calcium deposits
-
Low life expectancy of boiler
Chloride content
150 mg/l
Corrosion of alloyed materials