Installation
General
Connection of air/flue gas pipes
Flue gas and supply air connection
The EURON is suitable for use as
conventional or balanced Flue. The
flue that is connected must be
removable.
As with all flue systems, it must be
ensured that there is no short circuit /
cross-contamination
between
the
supply air and flue gas.
For flue gas safety
the EURON is
fitted with an flue gas temperature
safety limiter (set at 85°C), therefore
this does not need to be provided for
in the installation.
The combustion air supply
must be
ensured. In areas such as in a laundry
or workshop, a hair salon, in areas with
electroplating,printing or metalworking.
In such or similar cases the supply air
must be supplied from a outside the
building.
Condensate connection
For every m
3
of natural gas burnt, 0.7
to 1.0 litres of condensate is produced,
as a consequence of the very high
utilisation of energy. This of course
must be discharged from the boiler.
Due to its acidic nature, plastic piping
must be used for draining the
condense. The condensate must be
able to run off freely into a tundish (or
neutralization tank), therefore avoiding
a back-up of condensate into the
boiler. Please Refer to BS6798:2000
for guidance.
(See picture to right)
C
ondensate created in the flue must
also be allowed to drain away freely
with the same considerations as for
the boiler condesate. Local regulations
must
be
observed.
Prior
to
commissioning the siphon in the
EURON must be filled with water .
Connection to air/flue gas routing
For concentric air/flue gas routing only
original MHS accessory parts should
be used.
Condense
Connection