background image

20

TABLE 9

Once 

“OPEN” command  

Activates the automation as described in Table 3 (Open function)

Twice 

“Pedestrian opening” command 

Activates partial opening of one or two leafs as described in Table 3  

 

  

(Pedestrian 

opening)

Three times 

“Open only” command 

Activates opening of the leaves (open - stop - open etc.)

Four times 

“Close only” command 

Activates closing of the leaves (close - stop - close etc.)

Five times 

“Stop” command 

Stops the manoeuvre

Six times 

“Apartment block open” command 

On opening the command has no effect, and on closing inverts movement, i.e.  

 

 

opening of the leaves

Seven times 

“High priority open” command 

Gives command even when automation is blocked

Eight times 

“Pedestrian opening 2” command 

Activates partial opening of the leaf M2, equal to approx. mid-travel

Nine times 

“Pedestrian opening 3” command 

Activates partial opening of the two leaves, equal to approx. mid-travel

Ten times 

“Open+ block automation” command 

It causes an opening manoeuvre, after which the automation is blocked;   

 

 

 

the control unit accepts no further commands with the exception of “Open high  

 

 

priority” and “Release” automation

Eleven times 

“Close + block automation” command 

It causes a closure manoeuvre, after which the automation is blocked;  

 

 

 

the control unit accepts no further commands with the exception of “Open high  

 

 

priority” and “Release” automation

Twelve times 

“Block automation” command 

It causes the manoeuvre to stop and the automation to block; the control unit   

 

 

accepts no further commands with the exception of “Open high priority” and “Release”  

  

automation.

Thirteen times  “Unblock automation” command 

It causes the automation to be released and normal operation to resume

10.4.3 - Remote memorisation

A new radio transmitter can be memorised on the control unit without 
having to use the unit itself. It is sufficient to have an “OLD” working and 
memorised radio transmitter. The “NEW” radio transmitter to be memo-
rised will inherit the characteristics of the OLD one, i.e. if the OLD radio 
transmitter was memorised in Mode 1, the NEW one will also be memo-
rised in Mode 1. In this case, during the memorisation stage you can 
press any key on the two transmitters. If, on the other hand, the OLD 
transmitter was memorised in Mode 2 you must press the key on the 
OLD transmitter which corresponds to the desired command, and the 
key on the NEW transmitter to which you wish to associate that com-
mand.
Holding the two transmitters, position yourself within the operating range 
of the automation and perform the following operations:

01.

  Press the key on the NEW radio transmitter for at least 5 s then 

release it.

02.

  Press the key on the OLD radio transmitter slowly 3 times.

03.

  Press the key on the NEW radio transmitter slowly once.

At this point the NEW radio transmitter will be recognised by the control 
unit and will assume the characteristics of the OLD one.
If there are other transmitters to be memorised, repeat all the steps 
above for each new transmitter.

10.4.4 - Deleting a radio transmitter

Only if the system features a radio transmitter, you can delete it from the 
memory by proceeding as follows.
If the transmitter is memorised in Mode 1, only one deletion procedure 
will be needed and at step 3 you can press any key. If the transmitter is 
memorised in Mode 2, one deletion procedure will be needed for each 
key memorised.

01.

  Press and hold key P1 

[B]

 (

fig. 36

) on the control unit.

02.

  Wait for the LED P1 

[A]

 (

fig. 36

) to switch on, so within three sec-

onds.

03.

  Press the key on the radio transmitter to be deleted for at least three 

seconds. If the deletion procedure is successful, the P1 LED will 
flash rapidly five times. If the P1 LED flashes only once slowly, it 
means that the deletion procedure has not been successful because 
the transmitter is not memorised.

04.

  To delete other transmitters keep key P1 pressed and repeat step 

3 within 10 seconds otherwise the deletion procedure will end auto-
matically.

36

B

A

10.4.5 - Deleting all the radio transmitters

With this operation all the memorised transmitters are deleted.

01.

  Press and hold key P1 

[B]

 (

fig. 36

) on the control unit.

02.

  Wait for LED P1 

[A]

 (

fig. 36

) to switch on, then off and then flash 3 

times.

3

 Release key P1 precisely upon the third flash.

4

 Wait approximately 4s for the deletion process to be completed; during 

this time the P1 LED will flash very quickly.

If the procedure is successful, after a few moments the P1 LED will flash 
slowly 5 times.

Summary of Contents for MhouseKit WS2S

Page 1: ...MhouseKit WS2S For power operated swing gate Installation instructions and warnings and operating manual IS0004A01EN_07 02 2012...

Page 2: ......

Page 3: ...12 7 2 INITIAL CHECKS 12 7 3 RECOGNITION OF CONNECTED DEVICES 12 7 4 RECOGNITION OF THE GATE LEAF OPENING AND CLOSING ANGLES 12 7 5 CHECKING THE RADIO TRANSMITTERS 12 7 6 SETTINGS 12 TESTING AND COMM...

Page 4: ...ed conformity of the automation In consideration of this all mains connection testing commissioning and mainte nance operations must be performed exclusively by a qualified and skilled technician All...

Page 5: ...Tx and Rx Ensure that all devices to be installed are in a sheltered location and protected against the risk of accidental impact 3 2 PRODUCT APPLICATION LIMIT Before proceeding with installation perf...

Page 6: ...position of all connection cables Refer to the instructions in paragraph 4 2 to establish the layout of the raceways for electric cable ducting 4 1 3 Ensure all equipment and materials for work are av...

Page 7: ...5 D G B C D D E F a d g d e f b b c 1 3 4 5 A B E H F I 2 L G D C A...

Page 8: ...ed to the leaf material 12 Turn the leaf to the required gate open position Place the limit switch against the straight arm L and tighten the two screws M fig 15 13 Loosen screw N securing the straigh...

Page 9: ...7 8 10 NO 11 E D C 12 13 9 A B F G...

Page 10: ...8 M L 15 17 N O P 16 Blue Yellow Green Brown 18 19 I 14 H H...

Page 11: ...9 OPEN STOP TX TR ECS M M FLASH STOP OPEN M M bus ECS bus ECS FLASH bus M M M M WS1SCM2 WS1SK M1 KS100 PH100 FL100 Blue Yellow Green Brown B A 20...

Page 12: ...electrical cable in the relative terminals of both TX and RX fig 21 5 and to the blue terminal on the control board No polarity needs to be observed 07 Fix the covering shell D in fig 21 6 with the t...

Page 13: ...11 22 A B 6 mm x4 6 mm x4 A B A B A B A A A A B B B 1 2 3 4 4 A B A B A B A B A B A B 5 6 7 8 9 11 12 10 A B A B...

Page 14: ...urred see paragraph 10 5 Troubleshooting The connected devices recognition stage can be repeated again at any time even after the installation for example if an additional photocell is installed just...

Page 15: ...ablish what tests should be conducted based on the risks involved and verify the compliance of the system with applicable regulations legis lation and standards in particular with all the provisions o...

Page 16: ...am e g fig 5 risk assessment and solutions adopted manufacturer s declaration of conformity for all devices used use appendix 1 EC declaration of conformity for components of WS2S 02 Affix a dataplate...

Page 17: ...six times Press T2 seven times Press T2 eight times Press T3 once Press T3 twice Press T3 three times Press T3 four times Press T3 five times Press T3 six times Press T3 seven times Press T3 eight ti...

Page 18: ...ly be made after completing all installation and pro gramming phases as the battery constitutes an emergency power supply To install and connect the buffer battery PR1 to the control unit refer to fig...

Page 19: ...te the energy consumed by the automation proceed as follows 05 On the table below select the box corresponding to the intersection between the line with the weight and the column with the opening angl...

Page 20: ...cognition of other devices Normally the recognition of the devices connected to the ECSBus and the STOP input takes place during the installation stage However if new devices are added or old ones rem...

Page 21: ...to memorise it If the memorisation procedure is successful the P1 LED will flash 3 times 03 If there are other transmitters to be memorised repeat step 2 within the next 10 s otherwise the memorisati...

Page 22: ...press any key on the two transmitters If on the other hand the OLD transmitter was memorised in Mode 2 you must press the key on the OLD transmitter which corresponds to the desired command and the k...

Page 23: ...tent the voltage value is not important approximately 10 30 VAC if there is voltage the problem is due to the lamp in this case replace the lamp with one having the same characteristics TABLE 10 fig...

Page 24: ...rmal operation and on possible faults see Table 13 Quick flashes 1 flash 1 second pause 1 flash 2 flashes 1 second pause 2 flashes 3 flashes 1 second pause 3 flashes 4 flashes 1 second pause 4 flashes...

Page 25: ...e is under way Action Cyclic operation Complete cyclic operation Perform the recognition phase see chapter 3 5 2 Recognition of leaf opening and closing angles Opening angle recognition phase is under...

Page 26: ...osing of the contact causes the OPEN command STOP input For normally open contacts and or for 8 2K constant resistance type contacts or normally closed contacts with recognition of the normal status a...

Page 27: ...1 6 m s approx 20 approx 20 Up to 10m for maximum TX RX misalignment of 5 the device can signal an obstacle even in the case of adverse weather conditions The device can be connected only to ECSBus n...

Page 28: ...d doors AM OOK coded modulation of radio carrier 433 92 MHz Rolling code with 64 Bit code 18 billion billion combinations 4 each key can be used for the different controls of the same control unit or...

Page 29: ...WS1SC WS1SK PH100 and FL100 conform to DIRECTIVE 2004 108 CE 108 EC OF THE EUROPEAN PARLIA MENT AND COUNCIL of 15th December 2004 regarding the approximation of member state legislation related to el...

Page 30: ...28...

Page 31: ...and made available to all users of the automation 11 1 Safety instructions Keep an eye on the moving door and keep at a safe dis tance until the door has completely opened or closed do not cross the...

Page 32: ...uch that a fault or an incorrectly balanced door could cause injury 11 5 Remote control battery replacement fig 43 When the battery charge is low the range of the transmitter is significantly reduced...

Page 33: ...ation address Complies with the essential requirements of the following directives 2006 42 EC Machinery Directive 2004 108 EEC Electromagnetic Compatibility Directive 2006 95 EEC Low Voltage Directive...

Page 34: ......

Page 35: ......

Page 36: ...Mhouse is a commercial trademark owned by Nice S p a Nice S p a Via Pezza Alta 13 Z I Rustign 31046 Oderzo TV Italy Tel 39 0422 85 38 38 Fax 39 0422 85 35 85...

Reviews: