Fig. 6.6. Current output 1, consistency.
CURRENT OUTPUT 1: consistency
Low (4 mA)
High (20 mA)
=
0.00 %
=
5.00 %
Filtering
Error situation:
=
1.0 s
20 mA
Cs =
3.51 %
...9.62 mA
Edit
Next
F 7
F 6
F 5
F 4
F 8
F 3
F 1
F 2
F 9
F 1 0
F 1 1
F 1 2
F 1 3
F 1 4
F 1 5
F 1 6
i
Fig. 6.7. Current output 2, temperature.
CURRENT OUTPUT 2: temperature
Low (4 mA)
High (20 mA)
=
0.00 °C
= 90.00 °C
Filtering
Error situation:
=
1.0 s
20 mA
Cs =
75.4 °C
... 16.05 mA
Edit
Next
The MCAi Field Connection Board contains current
outputs for consistency, temperature, and the relative
chemical content measurement. Current output 2 is
isolated, current output 3 non-isolated. A current output
for consistency is also provided among the connections
on the Display Unit.
After initial configuration and calibration, the cur-
rent output scaling is still UNDONE. Go from Main
Menu => Current Output, and scale the outputs.
6.B.1. Scaling the current output for consistency
Go from M
AIN
M
ENU
=> C
URRENT
O
UTPUT
(Current
output 1, Fig. 6.6). Press [F1&F2] E
DIT
to edit.
1. Enter the consistency value corresponding to the
low limit (4mA).
2. Enter the consistency value corresponding to the
high limit (20mA).
3. Enter the filtering time for the output (usually 1
second is suitable).
4. Select how the current output will react to error
situations, by pressing [F7&F8] R
OLL
ALARM
until
the required alternative appears:
- Freeze:when an error occurs, the value is frozen to
the level prior to the error.
- 0, 4 or 20 mA: the output is set to 0, 4 or 20 mA.
5. Press [F3&F4] S
AVE
to save the changes.
NOTE: Step 4, current output value during errors, is set
to all three outputs at the same time, in the “Current
Output 1” display!
6.B. Current Output Scaling
6.B.2. Scaling the current output for temperature
Go from M
AIN
M
ENU
=> C
URRENT
O
UTPUT
=> N
EXT
(Current output 2, Fig. 6.7). Press [F1&F2] E
DIT
to edit
the output.
1. Enter the temperature value corresponding to the
low limit (4mA).
2. Enter the temperature value corresponding to the
high limit (20mA).
3. Enter the filtering time for the output (usually 1
second is suitable).
4. Press [F3&F4] S
AVE
to save the changes.
NOTE: If required, the outputs 2 & 3 can be switched so
that current output 2 is scaled for chemical content,
output 3 for temperature. To do this, press N
EXT
=>
[F5&F6] T
EMP
-> C
HEMICALS
.
NOTE: Current output 2 is isolated, current output 3 non-
isolated.
Summary of Contents for kajaaniMCAi
Page 1: ...kajaaniMCAi Installation operating service manual W4610201 V2 5 EN for software version 2 5 ...
Page 59: ...kajaaniMCAi Installation Operating Service A1 W4610201 V2 5 EN App 1 Technical specifications ...
Page 61: ...kajaaniMCAi Installation Operating Service A2 W4610201 V2 5 EN App 2 Contents of delivery ...
Page 66: ...kajaaniMCAi Installation Operating Service A4 W4610201 V2 5 EN App 4 Spare parts ...
Page 68: ...kajaaniMCAi Installation Operating Service A5 W4610201 V2 5 EN App 5 Installation instruction ...