Page 20 of 34
File Name:
Doc#586p.docx
123 SYSTEM SETPOINTS
Engine Lockout
Latched
[No]
This setting determines if only a momentary input to the Engine Lockout input is
required to stop the engine after an automatic stop, or prevent it starting
automatically. Can only be activated at the factory by Metron.
124 SYSTEM SETPOINTS
Remote Start
Input Contact Type
[No]
This setting whether contact for remote start is either Normally Open (NO) or
Normally Close (NC)
Configure User Preferences
201 USER PREFERENCES
Set System Real
Time Clock
[17:03:52]
Set the current FD4 clock (24 hour clock).
202 USER PREFERENCES
Set System Date
[12/31/99]
Set the current FD4 date.
203 USER PREFERENCES
Set System Day
Of The Week
[Monday ]
Set the local day of the week.
204 USER PREFERENCES
Log System Pressure
Drop Events
[No ]
When this feature is enabled, the controller will log the current system
pressure in the event log when system pressure has dropped below the set
pressure value. Typically set to “No” as not to needlessly fill up the event
log.
205 USER PREFERENCES
Low Pressure Event
Trip Pressure
[ 0.0]psi 0-999
The desired pressure that will cause a log of system pressure in addition to the
normal periodic logging of system pressure.
206 USER PREFERENCES
Low Pressure Event
Reset Time
[ 5] seconds 0-20
The amount of time the pressure must be above the pressure setting in screen
205 before the Pressure Drop Event is logged as being cleared.
207 USER PREFERENCES
Time Between
Pressure Log Samples
[ 15] seconds 15-999
The frequency at which system pressure is automatically logged. Normally
set to 15 seconds. Lower values will increase the number of logged pressures
and fill up the memory in a shorter period of time.
211 USER PREFERENCES
Enable Remote
Keypad
[NO]
Remote
Keypad
212 USER PREFERENCES
LCD Back Light Mode
0=Always on
[0]] 1=Power Save
Set to Always on or to Power Save if it is desired to have the backlight
automatically shut off when no buttons have been pressed for a preset period
of time. This should only be done if battery power is limited and AC power is
not on.