Page 26 of 34
File Name:
Doc#586p.docx
If
the
original
SD
memory
card
is
no
longer
available
a
blank
SD
memory
card
(formatted
to
FAT)
can
be
used.
The
firmware
of
the
controller
will
create
the
necessary
log
files
and
will
continue
to
operate.
When
the
new
SD
memory
card
is
inserted
all
of
the
events
and
pressure
logs
that
were
missed
will
be
automatically
copied
from
the
internally
memory
to
the
new
SD
memory
card.
As
the
logs
are
copying
to
the
SD
card
the
OID
will
display
the
follow
message.
PLEASE WAIT....
CAPTURING UNSAVED
EVENT LOGS 13
PRESSURE LOGS 159
After
the
controller
has
finished
copying
the
logs
stored
internally
to
the
SD
card
the
alarms
will
be
cleared.
This
operation
can
take
a
few
seconds
up
to
many
minutes
depending
on
the
quantity
of
logs
to
copy
and
the
speed
of
the
SD
card.
2.
SD
Logging
Error
The
controller
can
detect
problems
logging
to
the
SD
card.
If
there
is
a
logging
error
the
panel
behaves
in
the
same
way
as
when
the
SD
card
is
removed.
The
only
difference
is
that
the
SD
card
will
still
be
in
the
control
panel.
The
controller
will
periodically
try
to
recover
from
logging
errors
and
if
successful
the
alarms
and
message
on
the
OID
will
clear.
However,
if
the
message
on
the
OID
continues
to
display
for
over
15
minutes
the
SD
card
should
be
replaced
with
a
new
card
or
the
old
card
can
be
reformatted
to
FAT
(not
FAT32
or
exFAT)
using
a
PC.
It
is
recommended
that
any
files
that
are
readable
from
a
PC
are
copied
before
the
card
is
reformatted.
3.
Description
of
the
files
stored
on
the
SD
memory
card
Filename
Description
EVENTS.TXT
The main log file. Contains a maximum of 3000 events occurred on the controller in date order. After
the 3000 limit is reached the oldest events will be overwritten from the top of the file.
FD4FW.HEX
Original firmware, Metron Eledyne use only.
FW_DEF.TXT
A file containing the version number of the FD4FW.HEX firmware file. Metron Eledyne use only.
SETTINGS.TXT This
file
is created when ‘save all settings’ is executed from the controller, contains the saved settings.
SCREENS.NEW
Data file used for the screen messages on the OID, Metron Eledyne use only.
MISCTEXT.NEW
Data file used for the messages on the OID screens, Metron Eledyne use only.
AUXALM.TXT
Obsolete. Replaced by SETTING.TXT but may still be on the SD card.
CONFIG.TXT
Configures the LEDs on the OID, Metron Eledyne use only.
PRESS**.TXT
Contains the pressure log where ** is the day of month 01 through 31. Each month will overwrite the
previous month’s data day by day. At the start of each matching day number the old file is deleted and
a new file recreated.
The
SD
card
may
contain
other
files.
Normally
these
would
be
drawings
or
other
documents
in
format.
See
Part
IX
above
for
a
description
of
the
format
of
the
pressure
and
event
log
files.