MI 3295 Step Contact Voltage Measuring System
MI 3295M Meter operation
18
Function
Parameter
Limit
Default value
Contact/Touch Voltage
Step Voltage
Iset
Iflt
Rinp
Ulim
10.0 A
1.0 kA
1.0 k
Ω
50V
Potential
Iset
Iflt
Step
Dir
10.0 A
10 A
1.0 m
0
°
Current
Type
Mode
Lim
A 1018
55 Hz
Off
5.4.4 Date and time
Date and time can be set in this menu.
Figure 5.7: Setting date and time
Keys:
Cursor LEFT / RIGHT
Selects the item to be changed.
Cursor UP
/
DOWN
Modifies selected item.
TEST
Confirms new setup and exits.
ESC
Returns to Settings main menu
.
5.4.5 Synchronization
Selecting SYNC. MI3295S will allow uploading different data from the Station to the Meter
and vice versa.
Options are:
Synchronization of date, time,
current and structure names
Uploading of test current results for
Step voltage, Contact/Touch voltage
and Potential calculation
Uploading of Earth resistance results
Figure 5.8: Synchronization menu
Keys:
Cursor UP
/
DOWN
Selects option.
TEST
Enters selected option.
ESC
Returns to Settings main menu
.