MI 3295 Step Contact Voltage Measuring System
Measurements
30
changing during the test the I
SET
parameter must be adjusted manually. The
measurement results cannot be corrected after the measurement.
7.2.3 Step voltage and Contact/Touch voltage measurements
While the Station injects the measuring current into earth the Step or Contact/Touch
voltage tests with the Meter can be carried out.
Figure 7.12:
Step and Contact/Touch voltage screens
Test parameters for Step voltage and Contact/Touch voltage measurement
I flt
Maximum expected fault current
(
1 A ... 200 kA)
I set, I gen
Test current
manually set (
10 mA
… 50 A )
or uploaded from Station
R inp
Input resistance
(
1 MΩ, 1 kΩ, 2 kΩ
(with additional adapter A 1304))
U lim
Limit step voltage
(25 V, 50 V)
Step or Contact/Touch voltage measurements
Select
STEP VOLT
or
U CONTACT/TOUCH
function.
Set test parameters / limits (optional).
For Step voltage place the test electrodes (see chapter
more information).
For Contact/Touch voltage place one test electrode and connect accessible metal
part (see chapter
Connect the test leads to the instrument.
Press the
TEST
key to perform the measurement.
Store the result by pressing the
MEM
key (optional).
Note:
The measurements can be carried out without synchronization. In this case the
measuring current must be controlled and set / changed manually. The results
cannot be corrected after the measurement.
Connections for Step voltage and Contact/Touch voltage measurement
Figure 7.13: Examples of Step voltage and Contact/Touch voltage measurement results
Displayed results for Step voltage and Contact/Touch voltage measurements:
U ............. calculated Step or Contact/Touch voltage
Um...........measured Step or Contact/Touch voltage