- 38 -
Installation manual
M-WRG-II M
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
9.14
Aligning the wall box on the outside before plastering
►
Fill the gaps between the wall box and wall aperture all around and continuously with
expanding foam or using another suitable filling material.
9.14.1 If the wall is less than 36.5 cm thick
► Use a Styrofoam saw to cut off the excess wall box (item 1 in Fig. 34 and Fig. 35) and
filler piece, if necessary (item 2 in Fig. 35), so that they are flush with the wall or any
attached insulation.
NOTICE
The wall box fixes the ventilation pipes with a 2° fall to the external wall.
► If the unplastered wall is thin (24 cm or less), do not cut off the wall box flush with
the unplastered wall. Allow the wall box to protrude into the external thermal insula-
tion composite system (ETICS) as this is the only way to allow the ventilation pipes
to pass far enough through and so be fixed in place.
► When fitting the ETICS, make sure that the ventilation pipes maintain their 2° fall.
9.14.2 If the wall is more than 36.5 cm thick
►
Compensate for thicker walls with continuous pipes. For walls that are 63 cm
thick or more, you will need 100 cm long outdoor and exhaust air pipes
(M-WRG-LR 100, part no. 5580).
NOTICE
The pipes must be continuous. Pipes that have been joined must not be used as there
is a risk of allowing condensation to penetrate into the wall area.
Fig. 34: Aligning the wall box
without
filler piece
1
Fig. 35: Aligning the wall box
with
filler piece
2
1