16
0:No multi-step control
R/W
Y
1: perform multi-step
control
R/W
Y
* 1. #400 ~ #407, #419 ~ #426, #438 ~ #445, #457 ~ #464: temperature Settings for each channel
segment. The unit is determined according to each input type. When the mode is Celsius, the unit is
0.1
℃
; when the mode is Fahrenheit, the unit is 0.1
℉
.
* 2. #408 ~ #415, #427 ~ BFM434, #446 ~ #453, #465 ~ #472: execution time of each channel segment.
When running multi-step Settings, the first stage execution time of each channel cannot be set to 0.
* 3. #416, #435, #454, #473: the starting segment number that needs to be repeated when setting the
multi-stept setting of each channel.
* 4. #417, #436, #456, #474: the termination number that needs to be repeated when setting the
multi-stept setting of each channel. The end segment number must not be less than the start segment
number of the channel, otherwise an execution error will result.
* 5. #418, #437, #457, #475: set the number of repeats for each channel.
* 6. #552: multi-step Settings enabled. #552 is effective with 8 bits less, the multi-stept setting function of
Bit0 control channel 1 is started, the multi-stept setting function of Bit1 control channel 2 is started, and
so on. When the mark is 0, start multi-paragraph setting; When the flag is 1, a multi-stept setting is
performed. When the multi-stept setting is executing, write 0 to stop the multi-stept setting. When you
write 1 again, the multi-stept setting will be reexecuted from the first segment.
1.5.5 Alarm function setting
The setting contents of the alarm function of the buffer of mtc-04-nvt (BFM) are shown in table 1-12.
Table 1-12 MTC-04-NVT buffer (BFM) alarm function Settings
BFM
Content
Remarks
Nature
Save
CH1
CH2
CH3
CH4
#600
Alarm 1 mode setting * 1
Default value :0
R/W
Y
#601
Alarm 2 mode setting * 1
Default value :0
R/W
Y
#602
Alarm 3 mode setting * 1
Default value :0
R/W
Y
#603
Alarm 4 mode setting * 1
Default value :0
R/W
Y
#604
Alarm dead zone setting
* 2
Default value :10,denoted
by 0.1
℃
R/W
Y
#605
Alarm delay times * 3
Default
value :0,range:0~255
Range:0~999
R/W
Y
#606 #610 #614 #618
Alarm 1 setting value * 4
Default value :0
R/W
Y
#607 #611 #615 #619
Alarm 2 setting value * 4
Default value :0
R/W
Y
#608 #612 #616 #620
Alarm 3 setting value * 4
Default value :0
R/W
Y
#609 #613 #617 #621
Alarm 4 setting value * 4
Default value :0
R/W
Y
* 1. #600 ~ #603: alarm enable, from which the user can determine the type of alarm required to enable.
#600 sets the alarm type 1, #601 sets the alarm type 2, and so on. Mtc-04-nvt offers 14 warning types,
four of which can be selected simultaneously (see 5.3.1 warning types). For different channels, the
warning values of 1 ~ 4 alarms determined by #600 ~ #603 are set by #606 ~ #609, #610 ~ #613, #614 ~
#617, and #618 ~ #621 respectively.
* 2. #604: set the dead zone for each channel's alarm mode. In order to avoid repeated occurrence of