Figure 6-4 Input D0,D1
6.Right-click the site 2 option under the module configuration in the left tree structure, and select
download from the right-click menu that pops up.
Figure 6-5 Download
7.The feature change is completed when the download site 2 configuration is completed in the lower left
corner of the interface.
6.2 PID control and alarm
Example: MTC station number is 2, set the first channel to use mode 3, work in the heating mode, the
given value is 100.0
℃
, the control cycle is 3 seconds, the proportional band is 20, the integral time is 60,
the differential time is 15; Use the upper limit temperature input value and the lower limit temperature
input value with waiting alarm. Other channels are closed (if used, set the same method as channel 1).