30
TORKEL 900-SERiES
ZP-CS01E
CS033663DE
6 EXTERNAL CURRENT MEASUREMENT
3]
Set max current on TORKEL 2.
4]
Set warning limits only on TORKEL 1.
5]
Set the stop limits. The voltage and test
period (time) can be set on each individual
TORKEL. Stopping after a certain capac-
ity (Ah) is reached can only be activated on
TORKEL 1.
Note
Only TORKEL No. 1 is to control the TXLs.
6]
Set switch <F1> to the upper (ON) position
on the TXLs.
7]
Then start the TORKEL that has the highest
number (when numbered as set forth above).
Now start the TORKEL with the second
highest number, then the third highest, etc.
Finally, start TORKEL 1.
Starting the TORKELs in this order prevents
the current from being higher than desired
at the beginning of the test.
Two or more TORKEL and TXL units
TORKEL 1 Measures the entire battery current.
TORKEL 2 Measures all current except the current
through TORKEL 1.
TORKEL 3 Measures all current except the currents
through TORKEL 2 and TORKEL 1 (and so
forth).
The last
TORKEL
Measures only the current through itself
and the TXLs.
Example with two TORKELs. The first TORKEL regulate the TXLs
and the second TORKEL contributes in the total regulation.
1]
Apply the clamp-on-probes as illustrated
above.
2]
Set the desired total current (same value) on
both (all) TORKEL units.
As a result, the maximum regulation capabil-
ity of all TORKEL units will be used. You do
not need to pay any attention to the mes-
sage reading “Cannot regulate” as long as it
does not appear on TORKEL No. 1.
3]
Set warning limits only on TORKEL No. 1.
4]
Set the stop limits. The voltage and test
period (time) can be set on each individual
TORKEL. Stopping after a certain capac-
ity (Ah) is reached can only be activated on
TORKEL No. 1.
Note
Only TORKEL No. 1 is to control the TXLs.
Only TORKEL No. 1 is to be connected to the
PC.
5]
Set switch <F1> to the upper (ON) position
on the TXLs.
6]
Then start the TORKEL that has the highest
number (when numbered as set forth above).
Now start the TORKEL with the second
highest number, then the third highest, etc.
Finally, start TORKEL No. 1.
Starting the TORKELs in this order prevents
the current from being higher than desired
at the beginning of the test.
Constant current, regular load
connected
A current shunt can be used instead of the DC clamp-on
current probe but this requires opening the current path
and connecting the shunt in series.
Summary of Contents for TORKEL 910
Page 2: ......
Page 13: ...CS033663DE ZP CS01E TORKEL 900 series 13 4 Menu system...
Page 27: ...CS033663DE ZP CS01E TORKEL 900 series 27 6 External current measurement...
Page 31: ...CS033663DE ZP CS01E TORKEL 900 series 31 7 Alarm function...
Page 33: ...CS033663DE ZP CS01E TORKEL 900 series 33 8 How to obtain the desired current...
Page 41: ...CS033663DE ZP CS01E TORKEL 900 series 41 10 Troubleshooting...
Page 43: ...CS033663DE ZP CS01E TORKEL 900 series 43 11 Calibration...
Page 45: ...CS033663DE ZP CS01E TORKEL 900 series 45 12 Specifications...
Page 49: ...CS033663DE ZP CS01E TORKEL 900 series 49 12 Specifications...
Page 51: ......