Performing Tests within Forms
AVTMDELTA4000-EN Rev 6 April 2018
61
NOTE
Exciting current measurements are pending voltage level. Make sure use
same voltage level as in earlier measurements on same transformer.
Exciting current may also vary due to core magnetization status, exciting
current measurements should be performed prior winding resistance
measurement or after demagnetization.
Multiple Quick Tests
Standards measurements may be complemented with additional measurements
executed from the Multiple Quick Test sub-form selected as a new test or as
manual measurements in the standard test forms. Check "Manual" in the select
test boxes and a Multiple Quick Test table will be added at the end of the form.
In the field "INSULATION TESTED" you enter information on what to be
tested, TEST MODE set/change the test mode, SUPPRESS set/change noise
suppression mode.
It is also possible to use Delta Control for controlling the test by clicking the
Delta Control button (above the table) in PowerDB form, Delta Control will
send all data to be stored in the Multiple Quick Test table.