Performing Tests within Forms
AVTMDELTA4000-EN Rev 6 April 2018
59
of the form. You should select the Number of Tests based on how many
transformer taps you intend to test.
The first test must measure the capacitance of the Standard Capacitor, in pico-
Farads (pF).
Connect the test set leads, the HV lead and the Red measurement lead, directly
to the capacitor.
Initiate the test by left clicking on the blue field for the Standard Capacitor.
Subsequent tests require the HV lead to be connected to one side of a HV
winding (e.g. H1/U/A) where the other side of the HV winding is grounded to
the tank (e.g. H0/N/N). The corresponding winding on LV side is grounded on
one side and on the other side is connected to Red lead via the capacitor.
By enter the winding voltage levels in the form, the assessment is automatic.