Unvented Hot Water Cylinder
14
Unvented Hot Water Cylinder
14
PRODUCT SPECIFICA
TION (1)
Limitations
• The Megaflo
Commercial
unvented water heater should not be used in any of the following
instances:
• Solid fuel boilers or any other boiler in which the energy input is not under effective thermostatic
control unless additional and appropriate safety measures are installed.
• Gravity circulation primaries.
• Steam heating plant unless additional and appropriate safety devices are installed.
• Ascending spray type bidets or any other Class 5 back syphonage risk requiring that a Type AA,
AB, AD or AG air gap be employed.
• Water supplies that have either inadequate pressure or where the supply may be intermittent.
• Situations where it is not possible to safely pipe away any discharge from the safety valves.
• Areas where the water consistently contains a high proportion of solids, eg. suspended matter
that could block the strainer, unless adequate filtration can be ensured.
• The installation must be carried out in accordance with the relevant requirements of the
appropriate Building Regulations: either The Building Regulations (England), The Building
Regulations (Scotland) or Building Regulations (Northern Ireland), The Water Fittings Regulations
(England and Wales) or Water Byelaws (Scotland).
Water supply
Bear in mind that the mains water supply to the property will be supplying both the hot and cold
water requirements simultaneously. It is recommended that the maximum water demand be assessed
and the water supply checked to ensure this demand can be met. A minimum flow rate of 100l/min
is required for the Megaflo
Commercial
range of cylinders
NOTE: A high mains water pressure will not always guarantee high flow rates.
Wherever possible the main supply pipe should be in 28mm. The minimum mains water supply
requirements should be 0.15 MPa (1.5 bar) working pressure and minimum 100 litres per minute
flow rate. At these values outlet flow rates may be poor if several outlets are used simultaneously,
the higher the available pressure and flow rate the better the system performance will be.
The water supply must be of wholesome water quality (Fluid Category 1 as defined by the Water
Supply Regulations 1999). The Megaflo
Commercial
is to be used for the storage of wholesome
water (max. 250mg/l chloride).
Water container:
Duplex stainless steel. 100% pressure tested to 2.25 MPa (22.5 bar).
Summary of Contents for Commercial 1000
Page 33: ...Unvented Hot Water Cylinder 33 MAINTENANCE AND SERVICING 3...
Page 34: ...Unvented Hot Water Cylinder 34 MAINTENANCE AND SERVICING 3...
Page 35: ...Unvented Hot Water Cylinder 35 USER GUIDE 4 NOTES...
Page 39: ...Unvented Hot Water Cylinder 39 USER GUIDE 4...
Page 40: ...Unvented Hot Water Cylinder 40 2011 7032408_issue_01...