Unvented Hot Water Cylinder
6
Unvented Hot Water Cylinder
6
PRODUCT SPECIFICA
TION (1)
Technical data (Indirect models in conformance with BS EN 12897:2006)
Maximum mains water supply pressure
2.5MPa (25 bar)
Operating pressure/PRV (low pressure system)
0.60MPa (6. bar)
Operating pressure/PRV (high pressure system)
1.00MPa (10 bar)
Expansion vessel pressure (low pressure system)
1.0MPa (10 bar max)
Expansion vessel pressure (high pressure system)
1.6MPa (16 bar max)
Expansion relief valve setting (low pressure system)
0.8MPa (8 bar)
Expansion relief valve setting (high pressure system)
1.3MPa (13 bar)
Maximum design pressure (low pressure system)
0.80MPa (8 bar)
Maximum design pressure (high pressure system)
1.3MPa (13 bar)
T&P relief valve setting
1.0MPa/90 °C (10 bar)
T&P relief valve setting
1.5MPa/90 °C (15 bar)
Primary coil operating pressure (max) - See Notes
1.0MPa (10 bar)
Auxillary Immersion heater rating (a.c. supply only) single phase
6kW & 9kW 50/60Hz ~
Auxillary Immersion heater rating (a.c. supply only) 3 phase
12kW - 54kW 50/60Hz ~
(See Accessories on page 29 for full range)
Storage
weights
(empty
and
full)
See
Table
5
Indirect
coil
ratings
See
Table
9
Pressure drop across the indirect coils
See table 10
Coil
surface
area
See
table
9
Notes:
The primary coil should not be exposed to more than 0.3MPa (3 bar) without the cylinder
being full of water and under minimum working pressure.
Summary of Contents for Commercial 1000
Page 33: ...Unvented Hot Water Cylinder 33 MAINTENANCE AND SERVICING 3...
Page 34: ...Unvented Hot Water Cylinder 34 MAINTENANCE AND SERVICING 3...
Page 35: ...Unvented Hot Water Cylinder 35 USER GUIDE 4 NOTES...
Page 39: ...Unvented Hot Water Cylinder 39 USER GUIDE 4...
Page 40: ...Unvented Hot Water Cylinder 40 2011 7032408_issue_01...