12.4 Signal Transmitter/ Reed Contact
12.4.2 Application / Function
The signal transmitter, in conjunction with products from Medenus GmbH, is used for monitoring
the position (position closed or open) of the safety shut-off valve via remote display.
A built-in neodymium magnet in the pull knob of the SSV and a set switching distance to the reed contact cause a sensor
to query the position of the safety shut-off valve and to transmit a signal via remote display. If the SSV drops into the
closed position, the switching distance will be exceeded and the sensor will lose the signal. This guarantees continuous
monitoring of the SSV control devices.
10.4.1 Use
•
On SAV control devices
22
6
2.8
4
3.2
2.7
Ø4
2.6
Optimum switching position
Switching
element
(pin no. 3)
OUT
black (pin no. 4)
Powe
r
suppl
y
(pin no. 1)
Load
DC(+)
brown
DC(-)
blue
12.4.4 ATEX marking
II 3G Ex nA II T5 X -10°C ≤ Ta ≤ +60°C
II 3D tD A22 IP67 T93°C X
•
Device group II
•
Category 3
•
Gas- (G) and dust-containing (D)
environments
•
Ex – conformity with European standards
•
nA – spark-free device
•
II – for all types of gas
•
T5 – temperature classification
•
tD – protected by a housing
•
A22 – for Zone 22
•
IP67 – type of protection
•
Ta – ambient temperature
• T93°C – max.
•
surface temperature
•
X – Special conditions, see instructions
12.4.3 Technical Data
Signal transmitter model
D-M9P(V
)
•
Wiring
3-wire
•
Output
PNP
•
Application
IC control/ PLC relay
•
Supply voltage
5/12/24VDC (4.5 to 28VDC)
•
Current consumption
max. 10 mA
•
Operating voltage
-
• Load current
max. 40 mA
• Internal voltage drop
max. 0.8 V
•
Leakage current
max. 100 μA at 24VDC
• Response time
max. 1 ms
•
Operational status indicator ON: red LED
•
Electrical inputs
potted cables
•
Connecting cables
oil-resistant vinyl cables
2.7 x 3.2 oval, 0.15 mm2,
3-wire
(D-M9P)
•
Shock resistance
1000 m/s2
•
Insulation resistance
max. 50M Ω at 500VDC Mega
•
Test voltage
AC 1000 V over 1 minute
(connecting
cable,
between
housings)
• Ambient temperature
-10 to 60°C
•
Degree of protection
IP67 IEC60529, JISC0920