40
© 05.2022
12.5 Inductive Signal Transmitter
12.5.2 Application / Function
The inductive transmitter, in conjunction with products from Medenus GmbH, is used for
monitoring the position (position closed or open) of the safety shut-off valve via remote display.
A sensor queries the position of the safety shut-off valve and a signal is transmitted via remote display. If the SSV drops
into the closed position, the switching distance will be exceeded and the sensor will lose the signal. This guarantees
continuous monitoring of the SSV control devices.
12.5.1 Use
•
On SAV control devices
Field of application
Certificate
Group, category, type of ignition protection
ATEX 1G
PTB 00 ATEX 2048 X
II 1G Ex ia IIC T6…T1 Ga The Ex-relevant
marking can also be printed on the enclosed adhesive
label.
ATEX 2G
PTB 00 ATEX 2048 X
II 1G Ex ia IIC T6…T1 Ga
The Ex-relevant marking is shown on the enclosed
adhesive label.
ATEX 3G (ic)
PF 13 CERT 2895 X
II 3G Ex ic IIC T6…T1 Gc
The Ex-relevant marking is shown on the enclosed
adhesive label.
ATEX 1D
PTB 00 ATEX 2048 X
II 1D Ex ia IIIC T135°C Da The Ex-relevant
marking can also be printed on the enclosed adhesive
label.
12.5.3 ATEX marking
12.5.4 Technical Data
•
Switching element function
NAMUR opener
•
Switching distance sn
2 mm
•
Installation flush
•
Safe switching distance sa
0 ... 1.62 mm
•
Reduction factor rAl
0.23
•
Reduction factor rCu
0.21
•
Reduction factor rV2A
0.7
•
Rated voltage Uo
8 V
•
Operating voltage UB
5 ... 25 V
•
Switching frequency f
0 ... 1000 Hz
•
Hysteresis H
1 ... 10 typ. 3 %
•
Reverse-polarity protection
yes
•
Short-circuit protection
yes
•
Current consumption
Measuring plate does not detect
3 mA
Measuring plate detects
1 mA
•
Switching state indication
Multi-hole LED,
yellow
•
EMC according to
IEC / EN 60947-
5-2:2004;
NE
21
•
Standards
DIN
EN60947-5-
6
(NAMUR)
• Ambient temperature
-25 ... 100 °C
(248
...
373
K)
• Storage temperature
-40 ... 100 °C
(233
...
373
K)
•
Connection type
V1 device plug
•
Enclosure material
Stainless steel
•
Front
face
PBT
•
Degree of protection
IP67
•
Use in hazardous area
see operating
instructions
•
Category
1G;
2G;
1D