45
© 05.2022
12.8 Fine Filter FF
12.8.2 Application / Function
Fine filters FF are intended to separate gas impurities such as dust, rust, and other solids in
gas-carrying lines at a defined point. They are used in the inlet pressure line between the actuator RSP and the regulator
R70. Fine filters FF can be used for gases according to DVGW work sheet G 260/G 262 and for neutral non-aggressive
gases. (other gases on request)
12.8.1 Use
•
for regulator R70
12.8.3 Technical Data
Type
FF
Max. allowable pressure PS
16 bar
Connection type
G 1/4“ for threaded pipe connections according to
DIN EN ISO 8434-1 (DIN 2353)
Material
Housing - Aluminum*
Filter
- Polyester-reinforced cellulose paper
Seals
- NBR
Temperature range
- 20°C to + 60°C
(operating/ambient temperature)
Filtration efficiency
Standard 99.9 % of the particle size > 2 µm
Recommended differential pressure
in pure state
50 to 100 mbar
Recommended differential pressure
for cartridge replacement
800 to 1,000 mbar
max. adm. differential pressure
2,000 mbar
Ex protection
The mechanical parts of the device do not have any
potential ignition sources of their own and therefore do not fall within the scope
of ATEX 95 (94/9/EC). Electrical components fitted to the device
comply with the ATEX requirements.
*)
Corrosivity category to DIN EN ISO 12944-2.
Categories C1 to C5-I are guaranteed without additional coatings.
For category C5-M, an epoxy resin coating is recommended.
Summary of Contents for RSP 254