background image

 9

 

00304

 

Detector Information 

AGDS-MCM 

v2

 

Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for.  
The descriptions below describe the position for each detector after considering these characteristics.  
 
For proper function care must be taken not to site a detector in a “dead space” or in the flow of any ventilation. 
 

Natural Gas/Methane 

Natural gas detectors should be mounted at high level on a wall approximately 150mm from the ceiling height and avoiding 
corners and potential dead air areas. 
 
Natural gas detectors should not be mounted below the height of the top of a doorway for example. This is because as the gas 
is slightly lighter than air it will rise filling the room from the ceiling down and will spill through the top of a door opening into the 
next room. If the detectors are mounted below this height then it will take longer the gas to reach the detector. 
 

LPG /Propane 

LPG gas is heavier than air so detectors need to be mounted at low level 100mm from the floor, consideration should be given 
to any potential mopping or wet floor height. 
 

Carbon Monoxide  

Carbon Monoxide is similarly weighted to air so detectors should be mounted between 1 to 2 meters from the floor. 
 

Carbon Dioxide  

Carbon Dioxide detectors should be installed so they monitor the general level of CO2 within the area. They should be mounted 
above standing head height and between 1m and 3m from the potential source. Care should be taken so they are not located 
close to the edge of a canopy or in direct flow of the supply or extract ventilation. 
 

For additional information or guidance on site specific requirements please don’t hesitate to contact us. 

Each detector has  its own Bi-Colour LED which is used to indicate the status of that detector. 
 
Not Lit:  

 

No power/comm’s. These a four wire units and all connections are required, check the polarity of both the  

 

 

 

power and the comm’s (MA/MB) terminals are correct. Check the detector is address to the correct channel  

 

 

 

and the detector has been learnt using (

21

 

Flashing Green: 

Detector is warming up, the detectors will flash green on power up for 90 seconds while the sensor  

 

 

 

 

elements stabilize. The system will ignore any detectors while flashing.  

 
Solid Green: 

 

Detector is powered and active.  

 

Flashing Red:   

Low level alarm. All detectors have both a low and high level alarm, low level alarms serve as a warning    

 

 

 

that an unsafe condition maybe building and gives chance to intervene before loss of gas service. 

 
Solid Red 

 

High level alarm. An unsafe level of the target gas have been reached and the system will isolate the  

 

 

 

 

gas supply. The cause of the alarm will require identifying and resolving before  the gas supply can be re-  

 

 

 

established. 

 
After installation a simple bump test can be performed by using an appropriate level test gas in order to check operation. Full testing and 
calibration checking takes place during a Medem commissioning. 

    Detector Location information 

    Detector Indications 

Summary of Contents for AGDS-MCM v2

Page 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Page 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Page 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Page 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Page 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Page 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Page 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Page 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Page 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Page 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Page 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...

Reviews: