background image

 3

 

00304

 

Main features

 

 

Connections to panel: marked on board 
 
1. 

Earth connection terminals. 

2. 

Live & Neutral 230 volts supply from 3amp switched fuse spur. 

3. 

230 volts out to gas solenoid valve. 

4. 

To contactor for isolating socket electricity supply, or fan (optional). 

5. 

Mains rated BMS relay set using switch 

18.

 

6. 

Mains rated BMS relay set using switch 

17.

 

7. 

Remote emergency stop and thermal links, SELV, connect in series multiple buttons (requires a N/C circuit). 

8. 

Extract fan interlock for current monitor (CM2M-K) or PD switches.  

9. 

Supply fan interlock for current monitor (CM2M-K) or PD switches.  

10. 

12 volt power for current monitor (CM2M-K). 

11. 

Power connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature. 

12. 

Comms connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature. 

13. 

Fire alarm input signal (N/C contact required).  

14. 

0-10 volt output to fan speed controllers based on CO2 and temperature levels. 

15. 

SELV Output for low power beacons/toners. Set using switch 

26

16. 

Enable/Disable internal toner. 

17. 

BMS relays settings for relays AUX 1 (

5

) and (

A

) See page 6. 

18. 

BMS relays settings for relays AUX 2 (

6

) and (

B

) See page 6. 

19. 

See page 7. 

20. 

Fan comm button, enables commissioning of the gas supply without fans running. 

21. 

Learn field device button, press once only when all detectors are connected and powered (verify with detectors button). 

22. 

Lift Valve - will power open the gas valve (

2

) while the button is held down. 

23. 

CO2 alarm level adjustment depending on application. Factory set for model & use. 

24. 

Timer adjustment for fan commissioning, allows timed period for gas installation commissioning. 

25. 

See page 7. 

26. 

Setting for VBMS (

15

). See page 6. 

27. 

See page 7. 

28. 

See page 7. 

29. 

OPTFAN Enable/Disable the front panel “FANS” LED (switch on to disable). 

24 

23 

11

9  10 

13 

12 

14 

16 

18 

17 

19 

26 

25 

28 

27 

29 

20  21  22 

15 

See page 6 for settings 

AGDS-MCM 

v2

 

Summary of Contents for AGDS-MCM v2

Page 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Page 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Page 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Page 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Page 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Page 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Page 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Page 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Page 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Page 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Page 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...

Reviews: