background image

 6

 

00258

 

 

Unused 

OFF 

OFF 

OFF 

OFF 

Unused 

ON 

OFF 

OFF 

OFF 

Unused 

OFF 

ON 

OFF 

OFF 

Fan Fault - FF 

ON 

ON 

OFF 

OFF 

EM Stop - ES 

OFF 

OFF 

ON 

OFF 

Fire Panel Active -FA 

ON 

OFF 

ON 

OFF 

High Alarm (Any State) - HA 

OFF 

ON 

ON 

OFF 

Low Alarm (Any State) - LA 

ON 

ON 

ON 

OFF 

Gas On  State 

OFF 

OFF 

OFF 

ON 

Detector Fault 

ON 

OFF 

OFF 

ON 

Generic Fault (FF,ES,FA,HA 

OFF 

ON 

OFF 

ON 

Key Switch State 

ON 

ON 

OFF 

ON 

There are five relays on the system which can be used for connecting to a BMS or sounder/Beacon etc., these 
can be set for switching to various conditions using the table below. There are two mains rated (

AUX

) and three 

SELV (

BMS

 
Two Mains rated (230v 5amps) 
Three SELV relays. (48 volts 1 amp) 
 

AUX 1

 and 

BMS A

: are set using switch 

17 

AUX 2

 and 

BMS B

: are set using switch 

18

 

 

BMS C

: Fixed condition, changes state on Gas Switch On/Off only. 

 
Settable conditions via dip switches (One condition selectable for each pair of relays)  

     BMS Relay Mains & SELV PCB 

System Settings 

AGDS-MCM 

v2

 

18 

17 

Summary of Contents for AGDS-MCM v2

Page 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Page 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Page 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Page 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Page 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Page 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Page 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Page 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Page 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Page 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Page 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...