Option Switches 

AGDS-MCM 

v2

 

     15 & 26 V BMS 

Terminal (

15

) VBMS is a nominal 20v output for use with external beacons, sounders etc. 

The output can be switched from 0 to +VE dependant on the setting of DIP switch (

26

)  

DIP switch options and setting are as per the table above 

     Option switch settings 19, 25, 27 & 28 

There are various option switches available on the system for accommodating some of the more common 
situations 

 

 

There always needs to be careful consideration to risk when changing any of the default settings, Medem (UK) 
Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented. 

 

28 

OPT  A  Spare 
OPT  B  Auto restart on power failure and fire alarm (off by default) 

2MAR 

Two minute delay to the auto restart - allows downstream appliances flame failure   
devices to close 

OPTX 

Spare 

27 

OP  C  Disables isolating gas on CO2 high alarm. CM & CO still isolate as normal 
OP  D    
OP  E  Changes detector time to isolate from 5s to 45s for CM & CO 
OP  F  Changes CO alarm levels from 20 & 30 PPM to 80 & 100PPM 

19 

OPT  G  Fan run time using "FRUN" button 
OPT  H  Spare 

OPT  I 

Allows BMS relays to indicate gas detector status when main "Gas On" switch is off 

OPT  J 

Spare 

25 

OP  K  Spare 
OP  L 

Spare 

OP  M  Spare 
OP  N  Spare 

Summary of Contents for AGDS-MCM v2

Page 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Page 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Page 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Page 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Page 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Page 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Page 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Page 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Page 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Page 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Page 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...